Ratings
Rated supply voltage (see note 1)
Operating voltage range
No-voltage input (see note 2)
Power consumption
Control outputs
Note: 1. A power supply with a ripple of 20% max. (single-phase power supply with full-wave rectification) can be used with each DC Model.
2. For contact input, use contacts which can adequately switch 0.1 mA at 5 V.
38
100 to 120 VAC (50/60 Hz), 200 to 240 VAC (50/60 Hz), 24 VAC/VDC (50/60 Hz), 48 VDC,
100 to 125 VDC
85% to 110% of rated supply voltage
ON-impedance:
1 kΩ max.
ON residual voltage: 1 V max.
OFF impedance:
500 kΩ min.
100 to 120 VAC:
approx. 0.23 VA (0.22 W) at 120 VAC
200 to 240 VAC:
approx. 0.35 VA (0.3 W) at 240 VAC
24 VAC/DC:
approx. 0.17 VA (0.15 W) at 24 VAC
approx. 0.1 W at 24 VDC
48 VDC:
approx. 0.18 W at 48 VDC
100 to 125 VDC:
approx. 0.5 W at 125 VDC
Contact output: 5 A at 250 VAC/30 VDC, resistive load (cosφ = 1)