Input Connections - Omron H3CR-A Manual

Hide thumbs Also See for H3CR-A:
Table of Contents

Advertisement

H3CR-A

Input Connections

H3CR-A/-AS
The inputs of the H3CR-A/-AS are no-voltage (short-circuit or open) inputs.
No-voltage Inputs
No-contact Input
(Connection to NPN open
collector output sensor.)
12 to 24 VDC
(sensor power supply)
+
DC power
supply
Timer
Sensor
5 Gate
6 Start
7 Reset
2 Input (0 V)
Operates with transistor ON
No-voltage Input Signal Levels
No-contact
1. Short-circuit level
input
Transistor ON
Residual voltage: 1 V max.
Impedance when ON: 1 kΩ max.
2. Open level
Transistor OFF
Impedance when OFF: 100 kΩ min.
Contact
Use contacts which can adequate-
input
ly switch 0.1 mA at 5 V
18
Contact Input
Timer
5 Gate
6 Start
7 Reset
2 Input (0 V)
Operates with relay ON
No-contact Input
(Connection to a voltage
output sensor.)
12 to 24 VDC
(sensor power supply)
+
DC power
supply
Timer
Sensor
5 Gate
6 Start
7 Reset
2 Input (0 V)
Operates with transistor ON
H3CR-A