Installation: Product Specifications

Location Limitations
This ice system is made up of three parts, the ice
making machine, or head; the remote condenser; and
the interconnecting tubing. The ice making machine
must be installed indoors, in a controlled environment.
Space must be provided near the machine for service
access. The remote condenser may be installed
above or below the ice machine, per the limits stated
later in this manual. The remote condenser may
be installed outdoors within the temperature limits
listed below. The interconnecting tubing must be
installed per the directions stated in this manual,
and the amount of tubing exposed to uncontrolled
temperatures must be minimized.
Space Limitations
Although the machine will function with no clearance
to the top and sides, some space must be allowed
for service access. Building the machine in with no
access will cause higher service cost, in many cases
this extra cost may not be covered by warranty.
Environmental Limitations, ice machine:
Minimum
Air temperature
50
F.
o
Water
40
F.
o
temperature
Water pressure
20 psi
Remote condenser
Air temperature
Power Supply
208-230 volt
model
Warranty Information
The warranty statement for this product is provided
separately from this manual. Refer to it for applicable
coverage. In general warranty covers defects
in material and workmanship. It does not cover
maintenance, corrections to installations, or situations
when the ice machine is operated in circumstances
that exceed the limitations printed above.
Product Information
The machine is a specialized version of a modular
cuber. A modular cuber does not include any ice
storage, it is designed to be placed onto an ice
storage bin. Many installations only require the
matching bin, but some may need an adapter to be
Maximum
placed between the ice machine and the bin.
100
F.
o
Additionally, the machine must be connected to the
100
F.
o
correct remote condenser and use the correct pre-
charged tubing. The machine is supplied with a full
80 psi
refrigerant charge, field charging is not required.
This product cannot be stacked.
January 2015
Page 3
Minimum
Maximum
-20
F.
120
o
o
Minimum
Maximum
198 volts
253 volts
F.