Precharged Line Routing - Scotsman C2648 Service Manual

Modular cuber induding prodigy plus
Hide thumbs Also See for C2648:
Table of Contents

Advertisement

C2648 Prodigy and Prodigy Plus Service Manual

Precharged Line Routing

Do not connect the precharged tubing until all routing
and forming of the tubing is complete. See the
Coupling Instructions for final connections.
Important: CONFIRM that the correct line set
(RTEL prefix) has been provided.
1. Each set of pre-charged tubing lines contains
a 1/2" diameter liquid line and a 5/8" diameter
discharge line.
Note: The openings in the building ceiling or wall,
listed in the next step, are the minimum sizes
recommended for passing the refrigerant lines
through.
2. Have the roofing contractor cut a minimum hole
for the refrigerant lines of 2". Check local codes,
a separate hole may be required for the electrical
power supply to the condenser.
Minimize tubing
routed outside
of the controlled
space
Caution: Do NOT kink the refrigerant tubing while
routing it.
3. Route the refrigerant tubes thru the roof opening.
4. Follow straight line routing whenever possible.
Excess tubing may EITHER be coiled up INSIDE
the building OR cut out prior to connection to the
ice maker and condenser.
If the excess tubing is cut out, after re-brazing the
tubing must be evacuated prior to connection to the
ice maker or condenser.
If the excess tubing is to be coiled, spiral it
horizontally to avoid excess trapping in the lines.
5. Have the roofing contractor seal the holes in the
roof per local codes
January 2015
Page 11
Best Practice: Coil
excess tubing inside
the building in a
horizontal coil.

Advertisement

Table of Contents
loading

Table of Contents