Hysteresis/Hysteresis Booster Heater - Viessmann VITOCAL 300-A Installation And Service Instructions Manual

Compact heat pump with electric drive
Table of Contents

Advertisement

Max. temperature
Danger
DHW with temperatures in
excess of 60 ºC can cause
scalding.
To limit the temperature to
60 °C, install a mixing device,
e.g. an automatic thermostatic
mixing valve (DHW cylinder
accessory).

Hysteresis/Hysteresis booster heater

Parameter
6007 Hysteresis
Relative to heating by heat pump.
Parameter
6008 Hysteresis booster heater
Relative to heating with an instanta-
neous water heater, an external heat
source or an electric immersion hea-
ter EHE (DHW cylinder accessories).
These settings determine the devia-
tion from the set DHW cylinder tem-
perature ("DHW cylinder temp.") at
which the cylinder heating is switched
on and off by the heat pump ("Hys-
teresis").
If an additional booster heater is
installed, the "Hyst. booster heater"
parameter is also relevant.
(cont.)
Access
"Device settings"
"Programming"
"DHW"
y to"Max. temp."
T or U
Standard setting
Setting range
A Set DHW temperature
B Heat pump switching hysteresis
C Switching hysteresis, instanta-
D Actual DHW temperature at the
E Heat pump control state
F Control state, instantaneous heat-
G OFF
H ON
DHW control settings
60 °C
20 to 80 °C
("Hysteresis")
neous heating water heater
("Hyst. booster heater")
upper cylinder temperature sen-
sor
ing water heater
147