System Diagram; Language Selection - Viessmann VITOCAL 300-A Installation And Service Instructions Manual

Compact heat pump with electric drive
Table of Contents

Advertisement

System definition control settings

System diagram

Parameter
7000
Select the system diagram during
commissioning.
This selection automatically enables
and monitors all components asso-
ciated with the respective scheme.
Access
"Device settings"
"Programming"

Language selection

Parameter
7001
Temperature differential heating
Parameter
7003
The heating limit temperature defines
the value of the outside temperature
below which central heating com-
mences.
The heating limit temperature is the
result of the selected set room tem-
perature less the value entered under
"Temp. diff. heating".
Example:
The selected set room temperature is
20 °C; the temperature entered under
"Temp. diff. heating" is 4.0 K.
Central heating commences if the
adjusted outside temperature drops
below 16 °C (heating limit tempera-
ture).
132
"System definition"
"System diagram"
l or m
Standard setting
Setting range
Note
For further information, see page 22.
Operating instructions
If the adjusted outside temperature
exceeds 18 °C, central heating stops
(because of the specified hysteresis
of 2 K).
2
0 to 11