Technical Data; Dc/Ac; Sunny Boy 3000Tl-Us - SMA Sunny Boy 3000TL-US Installation Manual

Pv inverter
Hide thumbs Also See for Sunny Boy 3000TL-US:
Table of Contents

Advertisement

SMA America, LLC

13 Technical Data

13.1 DC/AC

13.1.1 Sunny Boy 3000TL-US

DC Input
Maximum DC operating power
Maximum system voltage
Rated MPP tracking voltage range
Rated operating voltage
Minimum operating voltage
Start voltage, no-load status
Maximum operating current
Maximum input current per MPP tracking input
Maximum short-circuit current per
MPP tracking input
MPP tracking inputs
Strings per MPP tracking input
AC Output
Rated power at 208 V, or 240 V, 60 Hz
Maximum apparent power
Nominal AC voltage
AC voltage range at 208 V nominal
AC voltage range at 240 V nominal
Nominal AC current at 208 V
Nominal AC current at 240 V
Maximum output current
Maximum overcurrent protection
Total harmonic distortion
Nominal AC frequency
AC frequency range at 60 Hz nominal
Power factor at rated power
Connection conductor
Output connections
Installation Manual
13  Technical Data
3,200 W
600 V
175 to 480 V
400 V
125 V
150 V
18 A
15 A
19 A
2
2
3,000 W
3,050 VA
208 V / 240 V
183 V to 229 V
211 V to 264 V
14.5 A
12.5 A
15 A
30 A
≤ 4%
60 Hz
59.3 Hz to 60.5 Hz
1
2
L1, L2, N, PE
SB3-5TLUS22-IA-en-12