SMA Sunny Boy 3000TL-US Installation Manual page 67

Pv inverter
Hide thumbs Also See for Sunny Boy 3000TL-US:
Table of Contents

Advertisement

SMA America, LLC
Event number
7102
7105
7106
7110
7201 to 7202
7303
Installation Manual
Display message
Parameter file not
found or defective
Param. setting failed
Update file defect.
No update file found
Data stor. not poss.
Update main CPU
failed
Cause and corrective measures
The parameter file was not found or is defective.
The update failed. The inverter continues feeding
power into the grid.
Corrective measures:
• Copy the parameter file into the SD card
drive:\PARASET directory.
Parameters cannot be set via the SD card. The
inverter continues feeding power into the grid.
Corrective measures:
• Check the parameters for valid values.
• Ensure change rights via SMA Grid Guard
code.
The update file is defective. The update failed.
The inverter continues feeding power into the
grid.
Corrective measures:
• Re-format the SD card.
• Re-save the files to the SD card.
No new update file was found on the SD card.
The update failed. The inverter continues feeding
power into the grid.
Corrective measures:
• Copy the update file into the SD card
drive:\UPDATE directory.
Internal device fault, the inverter continues
feeding power into the grid.
Corrective measures:
• If this error occurs frequently, contact the
SMA Service Line.
Internal device fault. The inverter continues
feeding power into the grid. In very rare cases,
the firmware is damaged and the inverter
interrupts the feed-in.
Corrective measures:
• Contact the SMA Service Line.
SB3-5TLUS22-IA-en-12
11  Troubleshooting
67