Wiring Detail with Utility Load Shedding - Alternate Wiring Method
NOTE: This alternate wiring method is not applicable to early production XC17, XP17, XC21 and XP21 outdoor
units that used outdoor control 101796xx, 101797xx, 101798xx and 101799xx.
Outdoor Control Part Numbers
Figure 28. Non-Preferred Method - Outdoor Control- 103369-01 and 103369-02 Only)
XP17
XC21 iComfort™ Outdoor Unit
103369-01
103369-02
Remove existing wire
to contactor coil.
Utility Load Control Receiver
Contacts (N.C. contacts shown,
verify contact configuration)
Page 51
Compressor
Contactor