Chapter 4 – Configuration
19.2
DNP3 configuration example
19.2.1 Adding digital channels
92
To add binary data to the DNP3 slave database (RPV311), it's just necessary to add a
digital channel in the equipment's configuration, as shown at section 6. At the
RPV311 restarting proccess, the DNP3 library reads the configuration archive and
adds digital channels sequentially, associating to an integer number plus an
increment, starting at zero, for each digital channel. GOOSE digital channels are not
added to the DNP3 database.
First step for digital channel DNP3 database association is to create a digital channel.
Figure 43
shows the digital channels configured and table below shows associated
number at the DNP3 database for each digital channel of the example.
Figure 43: Digital Channels Configured
RPV311
RPV311-TM-EN-7