Chapter 17 – Technical Specifications
RPV311-TM-EN-7
IEC 61000-4-
16:1998+A2:2009
IEC 61000-4-17:1999
IEC 61000-4-18:2006
Test level: 40% residual voltage
Duration time
a.c.: 12 cycles
d.c.: 200ms
Test level: 70% residual voltage
Duration time
a.c.: 30 cycles
d.c.:500ms
A.C. and d.c. voltage interruptions
Test level: 0% residual voltage
Duration time
a.c.: 300 cycles
d.c.: 5s
Test frequency: 16,7 Hz, 50 Hz and 60 Hz
Test Voltage: 100V (differential mode)
with 1 sec dwell time
-Coupling resistor 100 Ω
-Coupling capacitor 0,047µF
300V (common mode) with 1 sec dwell
time
-Coupling resistor 200 Ω
-Coupling capacitor 0,47µF
Number of repetition: 3
Test level: 15 % of rated d.c. value
Test frequency: 120Hz, sinusoidal
waveform.
Voltage oscillation frequency: 1MHz
Differential mode: 1kV peak voltage;
Common mode 2,5kV peak voltage
RPV311
271