RPV311
Figure 112: Connection between RPV311 and the RA331, RA332 or RA333
RPV311-TM-EN-7
The RA331 and RA332 modules each occupy one physical link of the processing
module. The RA333 occupies two physical links of the processing module, one for
data transmission of analog channels (DFR) and the other for data transmission of
TW channels (TW).
On the RA331, RA332 and RA333 (TW and DFR) modules, each link has an indicator
showing the state of the connection with the processing module, as shown in
111. These indicators, L
light up when the link is active (i.e. it is receiving requests of the processing module).
Figure 111: RA331, RA332 and RA333 fiber optic connectors
The connectors are identified as RX for receiving data and TX for transmitting data.
The corresponding fibers must be linked to the acquisition module so that the TX of
RPV311 is connected to the RX of the RA331, RA332, or RA333 and RX of RPV311 is
connected to the TX of the RA331, RA332, or RA333, according to
and A
, on the front panel and back panel, respectively,
INK
CT
Chapter 15 – Installation
Figure
Figure
112.
222