Chapter 15 – Installation
14.1.1 Connection diagram of the DC transducer inputs of ± 10 V
15
Analog DC Transducer Inputs ± 20 mA
RPV311-TM-EN-7
Place the board back in the case.
Secure the case by screwing the back panel and connecting the terminals cables.
Connections shall use insulated flexible wires of 1.5 mm² cross section, 8 mm ring
terminals, and M3 holes.
Before making the electrical connection, make sure the signal is applied in
accordance with the technical specifications of the equipment. For information about
DC transducer inputs specifications, see Chapter 17: Technical Specifications.
Figure 124: Connection Diagram of DC Transducer Inputs ± 10 V
The RA331, RA332, and RA333 modules have up to 8, 16, or 8 analog inputs,
respectively, which can be configured for measurement of currents of DC
transducers of -20 mA to 20 mA. All channels are identified of 101 to 108 for the
RA331 and RA333, and 101 to 116 for the RA332.
Each analog input has three terminals: positive voltage, positive current and negative
terminal which are used for the current and for the voltage, as shown in
To define if the driver will measure current of a DC transducer it is necessary to select
an internal jumper in the module. The binary and analog inputs are galvanically
isolated.

Figure 125: Analog Input Terminals

RPV311
Figure 125.