1.3.2 TECHNICAL PARAMETERS OF HEATERS WITH TWO EXCHANGERS

TYPE
Tank capacity
Diameter
Weight
Operating hot service
water pressure
Operating heating
water pressure
Max temperature of
heating water
Max temperature of
hot service water
Upper exchanger
heat surface
Lower exchanger
heat surface
Lower/upper
exchanger
performance at
temperature drop
80/60 °C
Performance number
according to DIN
4708 upper
exchanger
Performance number
according to DIN
4708 lower
exchanger
Permanent HSW
performance* of
lower exchanger
Permanent HSW
performance* of
upper exchanger
HSW* heating time by
exchanger at
temperature drop
80/60 °C (lower/upper)
*HSW – Hot service water 45 °C
Table 2
OKC 300
NTRR/1MPa
NTRR/1MPa
l
295
mm
670
kg
124
MPa
1
MPa
1,6
°C
110
°C
95
2
m
1
2
m
1,5
kW
35/27
NL
2,9
NL
4,2
l/h
1100
l/h
670
min
24/16
OKC 400
OKC 500
NTRR/1MPa
380
470
700
700
144
183
1
1
1,6
1,6
110
110
95
95
1,05
1,3
1,8
1,9
57/31
65/40
3,4
5,9
15,2
19,1
1395
1590
740
970
20/14
23/16
OKC 750
OKC 1000
NTRR/1MPa
NTRR/1MPa
750
995
910
1010
245
315
1
1
1,6
1,6
110
110
95
95
1,17
1,12
1,93
2,45
60/33
76/32
6,2
7,1
21
26
1460
1490
815
780
37/28
43/37