Abnormal point and detection method
Error Code
Inlet water temperature
Abnormal if the following conditions are
detected for continuously 10 seconds.
1. Cooling mode
During compressor operation
TH32 < 3:
2. Heating mode (exclude defrosting)
PE
During compressor operation
TH32 < -10:
3. Defrosting mode
During compressor operation
TH32 < 0:
Thermistor
TH32: Inlet water temperature
9-4. HOW TO CHECK THE PARTS
PUHZ-W50VHA(-BS)
PUHZ-W85VHA(-BS)
PUHZ-HW112YHA(-BS)
PUHZ-HW140YHA(-BS)
PUHZ-HW140VHA2(-BS)
Parts name
TH3: Liquid pipe temp.
TH4: Discharge temp.
TH6: Plate Hex liquid pipe temp.
TH7: Ambient temp.
TH8: Heatsink temp.
TH32: Inlet water temp.
TH33: Comp. surface thermistor
(W50VHA(R1,R2), W85VHAR1)
Suction pipe temp. (HW112,140)
TH34: Comp. surface thermistor
(HW
HA2R3)
•
Fan motor (MF1)
Solenoid valve coil
<Four-way valve>
(21S4)
Compressor
(MC)
U
V
W
Linear expansion valve
(LEV-A) (LEV-B) (LEV-C)
<except
HW•HA2R3 models>
<HW•HA2R3 models>
Gray
M
1
M
2
Orange
3
Red
4
Yellow
5
Black
6
Solenoid valve coil
<Bypass valve>
(SV) W50,85
OCH439H
1 Reduced water flow
· Clogged filter
· Leak of water
2 Low temperature
· Low-load
· Low temperature inlet water
3 Defective water pump
4 Leakage or shortage of
refrigerant
PUHZ-W50VHAR1(-BS)
PUHZ-W85VHAR1(-BS)
PUHZ-HW112YHA2(-BS)
PUHZ-HW140YHA2(-BS)
PUHZ-HW140VHA2R1(-BS)
Disconnect the connector then measure the resistance with a tester.
(At the ambient temperature of 10 ~30 )
TH33 (W50VHA(R1,R2), W85VHAR1)
TH34 (HW
TH33 (HW112,140)
TH32
Refer to the next page.
Measure the resistance between the terminals with a tester.
(At the ambient temperature of 20 )
W50,85
2350±170
Measure the resistance between the terminals with a tester.
(Winding temperature 20 )
W50
0.640
Disconnect the connector then measure the resistance with a tester.
(Winding temperature 20°C)
Gray
Gray - Black
1
Orange
2
Red
3
Yellow
4
Black
5
Measure the resistance between the terminals with a tester.
(At the ambient temperature of 20 )
1450±150
Case
12 Check water piping.
3 Check water pump.
4 Check intake superheat.
PUHZ-W50VHAR2(-BS)
PUHZ-HW112YHA2R1(-BS)
PUHZ-HW140YHA2R1(-BS)
PUHZ-HW140VHA2R2-BS
Check points
Normal
TH4
160k ~410k
HA2R3)
•
TH3
TH6
4.3k ~9.6k
TH7
4.4k ~9.8k
TH8
39k ~105k
Normal
HW112,140
1435±150
Normal
W85
HW140V(2)
0.188
0.865 ~0.895
Normal
Gray - Yellow Gray - Orange
Gray - Red
46±3Ω
Normal
52
Judgment and action
Check leakage of refrigerant.
PUHZ-HW112YHA2R3(-BS)
PUHZ-HW140YHA2R3(-BS)
PUHZ-HW140VHA2R3(-BS)
Abnormal
Open or short
Abnormal
Open or short
Abnormal
HW112,140Y(2)
Open or short
0.302
Abnormal
Open or short
Abnormal
Open or short