Abnormal point and detection method
Error Code
Overvoltage or voltage shortage and
synchronous signal to main circuit
Abnormal if any of followings are detected
during compressor operation;
• Decrease of DC bus voltage to 310V
(50-140V only)
• Instantaneous decrease of DC bus voltage
50-140V : 200V
112,140Y : 350V
• Increase of DC bus voltage to
50V : 420V
85-140V : 400V
112,140Y : 760V
• Decrease of input current of outdoor unit
to 0.1A only if operation frequency is
more than or equal to 40Hz or compres-
sor current is more than or equal to 6A.
* Check U9 error detail (SW2 all ON)
Refer to 9-7.
U9
Overheat protection
Abnormal if outdoor pipe thermistor (TH3)
detects 70: or more or condensing
temperature of pressure sensor (63HS)
Ud
detects 70: or more during compressor
operation.
Compressor overcurrent interruption
(When compressor locked)
Abnormal if overcurrent of DC bus or
compressor is detected within 30 seconds
after compressor starts operating.
UF
OCH439H
Case
1 Decrease of power supply
voltage
2 Disconnection of compressor
wiring
3 Defective power circuit board
4 Disconnection or loose
connection of CN52C (50-140V)
5 Defective PFC module of
outdoor power board (50V)
6 Defective ACT module (85V)
7 Defective ACT module drive
circuit of outdoor power circuit
board (85V)
8 Disconnection or loose
connection of CNAF (85V)
9 Disconnection or loose
connection of CN7 on the outdoor
power circuit board/outdoor
converter board (112, 140Y)
0 Defective outdoor converter
circuit board (112, 140Y)
1 Defective current sensor of
outdoor noise filter board (50,
85V/112, 140Y)
2 Defective 52C drive circuit of
outdoor controller circuit board
(50-140V)
3 Disconnection or loose
connection of CN5 on the
outdoor power circuit board
(50, 85V)
4 Defective 52C drive circuit of
outdoor power circuit board
(112, 140Y)
5 Disconnection or loose
connection of CN2 on the
outdoor power circuit board
1 Defective outdoor fan (fan
motor) or short cycle of outdoor
unit during cooling operation
2 Defective outdoor pipe
thermistor (TH3)
3 Defective outdoor controller
board
4 Defective pressure sensor
1 Decrease of power supply
voltage
2 Looseness, disconnection or
converse of compressor wiring
connection
3 Defective compressor
4 Defective outdoor power board
5 Decreased water flow
6 Clogged filter of water pipe
7 Clogged plate heat exchanger
8 Locked water pump
9 Malfunction of water pump
48
Judgment and action
1 Check the facility of power supply.
2 Correct the wiring (U
V
W phase) to com-
pressor. Refer to 9-6 (Outdoor power circuit
board).
3 Replace power circuit board.
4 Check CN52C wiring.
5 Replace outdoor power circuit board.
(50V)
6 Replace ACT module. (85V)
7 Replace outdoor power circuit board. (85V)
8 Check CNAF wiring. (85V)
9 Check CN7 wiring. (112, 140Y)
0 Replace outdoor converter circuit board.
(112, 140Y)
1 Replace outdoor noise filter circuit board.
(50, 85V/112, 140Y)
2 Replace outdoor controller circuit board.
(50-140V)
3 Check CN5 wiring on the outdoor power cir-
cuit board. (50, 85V)
Refer to 9-6.
4 Replace outdoor power circuit board.
(112, 140Y)
5 Check CN2 wiring on the outdoor power cir-
cuit board. Refer to 9-6.
1 Check outdoor unit air passage.
23 Turn the power off and on again to check
the error code. If U4 is displayed, follow the
U4 processing direction.
4 Check pressure by microcomputer.
(Pressure sensor/ 63HS)
(SW2: Refer to 9-7.)
1 Check facility of power supply.
2 Correct the wiring (U
V
W phase) to
compressor.
Refer to 9-6 (Outdoor power circuit board).
3 Check compressor. Refer to 9-4.
4 Replace outdoor power circuit board.
5
9 Check water circuit and repair the defect.
~