Download Print this page
Ingersoll-Rand M801P040AU24AA Service Facts
Ingersoll-Rand M801P040AU24AA Service Facts

Ingersoll-Rand M801P040AU24AA Service Facts

Gas furnaces upflow & downflow – induced draft 1 stage heat
Hide thumbs Also See for M801P040AU24AA:

Advertisement

Quick Links

SERVICE FACTS
Gas Furnaces
Upflow & Downflow – Induced Draft
1 Stage Heat
Models:
M801P040AU24AA
M801P060AU24AA
M801P060AU36AA
M801P080BU36AA
M801P080BU48AA
IMPORTANT — This document contains a wiring diagram and service information. This is customer property and is to
remain with this unit. Please return to service information pack upon completion of work.
WARNING
MODEL
TYPE
RATINGS 2
Input BTUH 3
Capacity BTUH (ICS) 3
Temp. rise (Min.-Max.) °F.
BLOWER DRIVE
Diameter - Width (In.)
No. Used
Speeds (No.)
CFM vs. in. w.g.
Motor HP
R.P.M.
Volts / Ph / Hz
COMBUSTION FAN - Type
Drive - No. Speeds
Motor HP - RPM
Volts / Ph / Hz
FLA
FILTER — Furnished?
Type Recommended
Hi Vel. (No.-Size-Thk.)
VENT — Size (in.)
HEAT EXCHANGER
Type - Fired
- Unfired
Gauge (Fired)
ORIFICES — Main
Nat. Gas. Qty. — Drill Size
L.P. Gas Qty. — Drill Size
GAS VALVE
PILOT SAFETY DEVICE
Type
BURNERS — Type
Number
POWER CONN. — V / Ph / Hz 4
Ampacity (In Amps)
Max. Overcurrent Protection (Amps)
PIPE CONN. SIZE (IN.)
DIMENSIONS
Crated (In.)
WEIGHT
Shipping (Lbs.) / Net (Lbs.)
1 Central Furnace heating designs are certified to ANSI Z21.47 / CSA 2.3.
2 For U.S. applications, above input ratings (BTUH) are up to 2,000 feet, derate 4% per 1,000 feet for elevations above 2,000 feet above sea level. For Canadian applications,
above input ratings (BTUH) are up to 4,500 feet, derate 4% per 1,000 feet for elevations above 4,500 feet above sea level.
3 Based on U.S. government standard tests.
4 The above wiring specifications are in accordance with National Electrical Code; however, installations must comply with local codes.
NOTICE: The manufacturer has a policy of continuous product and product data improvement and
reserves the right to change design and specifications without notice.
© 2013 Ingersoll Rand
All Rights Reserved
M801P100BU36AA
M801P100CU48AA
M801P100CU60AA
M801P120DU60AA
M801P140DU60AA
DISCONNECT POWER BEFORE SERVICING
PRODUCT SPECIFICATIONS
M801P040AU24AA
Upflow / Horizontal
40,000
31,000
30 - 60
Direct
10 x 6
1
4
See Fan Performance Table
See Fan Performance Table
1/5
1080
115/1/60
Centrifugal
Direct - 1
1/50 - 3180
115/1/60
1.09
No
High Velocity
1 - 16x25 - 1 in.
4 Round
Alum. Steel
-
20
2 — 45
2 — 56
Redundant - Single Stage
Redundant - Single Stage
Hot Surface Ignition
Multiport Inshot
2
115/1/60
5.4
15
1/2
H x W x D
41-3/4 x 16-1/2 x 30-1/2
119 / 110
M801P060AD24AA
M801P060AD36AA
M801P080BD45AA
M801P100CD48AA
M801P100CD60AA
M801P060AU24AA
Upflow / Horizontal
60,000
47,000
30 - 60
Direct
10 x 6**
1
4
See Fan Performance Table
1/3
1075
115/1/60
Centrifugal
Direct - 1
1/50 - 3180
115/1/60
1.09
No
High Velocity
1 - 16x25 - 1 in.
4 Round
Alum. Steel
20
3 — 45
3 — 56
Redundant - Single Stage
Hot Surface Ignition
Multiport Inshot
3
115/1/60
9.0
15
1/2
H x W x D
41-3/4 x 16-1/2 x 30-1/2
41-3/4 x 16-1/2 x 30-1/2
127 / 118
M801-SF-1C
M801P120DD60AA
M801P140DD60AA
1
M801P060AU36AA
M801P080BU36AA
Upflow / Horizontal
Upflow / Horizontal
60,000
47,000
30 - 60
Direct
10 x 6**
1
4
See Fan Performance Table
1/3
1075
115/1/60
Centrifugal
Direct - 1
1/50 - 3180
115/1/60
1.09
No
High Velocity
1 - 16x25 - 1 in.
4 Round
Alum. Steel
20
3 — 45
3 — 56
Redundant - Single Stage
Hot Surface Ignition
Hot Surface Ignition
Multiport Inshot
3
115/1/60
9.0
15
1/2
H x W x D
41-3/4 x 19-1/2 x 30-1/2
127 / 118
80,000
63,000
30 - 60
Direct
10 x 7
1
4
1/3
1075
115/1/60
Centrifugal
Direct - 1
1/50 - 3180
115/1/60
1.09
No
High Velocity
1 - 17x25 - 1 in.
4 Round
Alum. Steel
20
4 — 45
4 — 56
Multiport Inshot
4
115/1/60
9.0
15
1/2
H x W x D
142 / 132
04/13

Advertisement

loading
Need help?

Need help?

Do you have a question about the M801P040AU24AA and is the answer not in the manual?

Questions and answers

Subscribe to Our Youtube Channel

Summary of Contents for Ingersoll-Rand M801P040AU24AA

  • Page 1 SERVICE FACTS M801-SF-1C Gas Furnaces Upflow & Downflow – Induced Draft 1 Stage Heat Models: M801P040AU24AA M801P100BU36AA M801P060AD24AA M801P120DD60AA M801P060AU24AA M801P100CU48AA M801P060AD36AA M801P140DD60AA M801P060AU36AA M801P100CU60AA M801P080BD45AA M801P080BU36AA M801P120DU60AA M801P100CD48AA M801P080BU48AA M801P140DU60AA M801P100CD60AA IMPORTANT — This document contains a wiring diagram and service information. This is customer property and is to remain with this unit.
  • Page 2 Service Facts PRODUCT SPECIFICATIONS MODEL M801P080BU48AA M801P100BU36AA M801P100CU48AA TYPE Upflow / Horizontal Upflow / Horizontal Upflow / Horizontal RATINGS 2 Input BTUH 3 80,000 100,000 100,000 Capacity BTUH (ICS) 3 64,000 79,000 79,000 Temp. rise (Min.-Max.) °F. 30 - 60 40 - 70 35 - 65 BLOWER DRIVE...
  • Page 3: Product Specifications

    Service Facts PRODUCT SPECIFICATIONS MODEL M801P060AD24AA M801P060AD36AA M801P080BD45AA M801P100CD48AA TYPE Downflow / Horizontal Downflow / Horizontal Downflow / Horizontal Downflow / Horizontal RATINGS 2 Input BTUH 3 60,000 60,000 80,000 100,000 Capacity BTUH (ICS) 3 48,000 64,000 80,000 48,000 Temp. rise (Min.-Max.) °F. 35 - 65 30 - 60 35 - 65...
  • Page 4: Safety Section

    Service Facts SAFETY SECTION WARNING WARNING CARBON MONOXIDE POISONING HAZARD The cabinet must have an uninterrupted or unbroken ground according to National Electrical Code, ANSI/NFPA Failure to follow the steps outlined below for each 70 - “latest edition” and Canadian Electrical Code, CSA appliance connected to the venting system being C22.1 or local codes to minimize personal injury if an placed into operation could result in carbon monoxide...
  • Page 5: Periodic Servicing Requirements

    Service Facts PERIODIC SERVICING REQUIREMENTS 1. GENERAL INSPECTION — Examine the furnace NOTE: installation annually for the following items: On LP (propane) units, due to variations in BTU content and altitude, servicing may be required at shorter inter- a. All flue product carrying areas external to the fur- vals.
  • Page 6 Service Facts UPFLOW WIRING DIAGRAM From Dwg. D344494 (continued on next page) M801-SF-1C...
  • Page 7 Service Facts UPFLOW SCHEMATIC DIAGRAM From Dwg. D344494 M801-SF-1C...
  • Page 8 Service Facts DOWNFLOW WIRING DIAGRAM From Dwg. D344495 (continued on next page) M801-SF-1C...
  • Page 9 Service Facts DOWNFLOW SCHEMATIC DIAGRAM From Dwg. D344495 M801-SF-1C...
  • Page 10 0.60 0.70 0.80 0.90 4-HIGH - Black 1018 1004 3-MED - HIGH - Blue M801P040AU24AA 2-MED - LOW - Yellow 1-LOW - Red 4-HIGH - Black 1018 3-MED - HIGH - Blue M801P060AU24AA 2-MED - LOW - Yellow 1-LOW - Red...
  • Page 11 Service Facts FURNACE AIRFLOW (CFM) VS. STATIC PRESSURE (ins. w.g.) MODEL SPEED TAP 0.10 0.20 0.30 0.40 0.50 0.60 0.70 0.80 0.90 4-HIGH - Black 1200 1155 1111 1056 1001 3-MED - HIGH - Blue 1025 M801P060AD24AA 2-MED - LOW - Yellow 1-LOW - Red 4-HIGH - Black 1480...
  • Page 12 Service Facts CONDITIONS AFFECTING UNIT The following warning complies with State of California law, Proposition 65. PERFORMANCE WARNING 1. EXCESSIVE COMBUSTION VENT PRESSURE OR FLUE BLOCKAGE This product contains fiberglass wool insulation! If pressure against the induced draft blower outlet becomes excessive, the pressure switch will shut off the Fiberglass dust and ceramic fibers are believed by the gas valve until acceptable combustion pressure is again...