Blower Speed Selection - Rheem R95P Installation Instructions Manual

(-)95p series
Table of Contents

Advertisement

TABLE 17
IR FLOW PERFORM NCE – (-)95P SERIES MODELS
Motor HP [W]
Model
Blower Size
IN [MM]
(-)95PA
1/4 [187]
0401
11 x 7
317MSA
[279 x 178]
(-)95PA
1/2 [373]
0601
11 x 8
317MSA
[279 x 203]
(-)95PA
1/2 [373]
0701
11 x 8
317MSA
[279 x 203]
(-)95PA
3/4 [559]
0851
11 x 10
521MSA
[279 x 254]
(-)95PA
3/4 [559]
1001
11 x 10
521MSA
[279 x 254]
(-)95PA
3/4 [559]
1151
11 x 11
524MSA
[279 x 279]
*Factory Setting For Heat
All shaded cells are valid heating settings. Do not use speed taps and/or static pressures which do not fall into the shaded cells on this table.
The furnace controls have four active quick connect termi-
nals for connecting the motor speed leads. These are:
1. FAN — motor runs on this speed when the thermostat
is in the "FAN ON" position.
2. COOL — connect desired cooling speed.
3. HEAT — connect desired heating speed.
4. H/C (for heat/cool) — connect desired speed when
heating and cooling speed are the same.
In addition to the active motor terminals, there are two
motor parking terminals (labeled M1 and M2) available for
placing any unused motor taps. All unused motor taps
should be connected to either M1 or M2. These terminals
(M1 and M2) will not be energized under any condition.
IMPORTANT: Do not connect any motor speeds to "HEAT"
and/or "COOL" if you use the "HEAT/COOL" terminal.
Speed Tap
0.1 [0.02]
0.2 [0.05]
Low
732
695
Med. Lo
875
845
Med. Hi*
1073
1049
High
1279
1239
Low
830
793
Med. Lo
940
908
Med. Hi*
1168
1139
High
1421
1385
Low
852
827
Med. Lo
986
955
Med. Hi*
1238
1211
High
1493
1452
Low
1313
1275
Med. Lo
1488
1452
Med. Hi*
1732
1704
High
1983
1929
Low
1329
1313
Med. Lo
1535
1498
Med. Hi*
1796
1748
High
2019
1961
Low
1249
1234
Med. Lo
1440
1429
Med. Hi*
1770
1750
High
2123
2077
CFM ir Delivery
External Static Pressure, "W.C. [kPa]
0.3 [0.07]
0.4 [0.10]
0.5 [0.12]
669
639
605
820
792
766
1004
975
943
1213
1174
1121
755
705
654
875
821
766
1109
1060
1010
1349
1291
1232
802
752
701
923
883
843
1183
1139
1094
1410
1364
1318
1236
1221
1184
1415
1384
1328
1676
1630
1579
1874
1810
1742
1296
1260
1224
1461
1422
1382
1700
1656
1612
1903
1843
1782
1219
1183
1146
1417
1381
1344
1730
1696
1662
2031
1983
1934
5. If heating and continuous fan speed are the same,
"piggyback" jumper across "FAN" and "HEAT" termi-
nals.
If cooling speed and fan speed are desired to be the same,
this may be accomplished by not connecting "Y" to the in-
tegrated furnace control.
IMPORTANT: If desired for cool, fan and heat to all be
the same speed, then "piggyback" jumper "H/C" to
"FAN" and do not connect "Y" to the integrated fur-
nace control. Do not connect anything to "Heat" or
"Cool."
See selection titled "Field Selections – Dipswitches" for
setting the heating and cooling blower off delay times.
0.6 [0.15]
0.7 [0.17]
0.8 [0.19]
547
512
487
726
659
605
900
864
798
1069
1033
980
599
544
496
710
653
584
942
874
802
1147
1062
976
662
623
580
790
737
686
1036
978
897
1257
1195
1084
1141
1098
1053
1279
1229
1170
1498
1417
1343
1663
1583
1477
1171
1117
1049
1325
1268
1203
1536
1460
1370
1687
1592
1489
1112
1078
1017
1313
1281
1221
1611
1559
1463
1856
1777
1665