Potterton Promax 15 HE Installation And Servicing Instructions page 14

Wall mounted powered flue condensing boiler gas firel central heating unit
Table of Contents

Advertisement

Q
D
J
Likely flue positions requiring
Fig. 17
a flue terminal guard
Terminal Position with Minimum Distance (Fig. 17)
A
Directly below an openable window, air vent or any other
ventilation opening.
B
Below gutter, drain/soil pipe.
C Below eaves.
D Below a balcony/car port roof.
E
From vertical drain pipes and soil pipes.
F
From internal or external corners.
G Above adjacent ground or balcony level.
H From a surface facing a terminal.
I
Facing a terminals.
J
From opening (door/window) in carport into dwelling.
K
Vertically from a terminal on the same wall.
L
Horizontally from a terminal on the same wall.
M Above an opening, air brick, opening window etc.
N Horizontally to an opening, air brick, opening window etc.
Vertical Flues - minimum distance to edge of terminal
P
Above the roof level (to base of terminal).
Q From adjacent wall to flue.
R From adjacent opening window.
S
From another terminal.
14
Supplied By www.heating spares.co Tel. 0161 620 6677
S
L
K
G
M
A
E
G
7.0 Site Requirements
7.9
Flue
NOTE: Due to the nature of the boiler a plume
of water vapour will be discharged from the
flue. This should be taken into account when
siting the flue terminal.
1. The following guidelines indicate the general
requirements for siting balanced flue terminals.
Recommendations for flues are given in BS 5440
Pt.1.
2. If the terminal discharges onto a pathway or
passageway, check that combustion products will
not cause a nuisance and that the terminal will
not obstruct the passageway.
3. Take into consideration the effect the plume of
vapour may have on neighbours when siting the
flue.
5. If a terminal is less than 2 metres (78
above a balcony, above ground or above a flat
roof to which people have access, then a suitable
terminal guard must be provided.
B,C
R
N
G
P
D
H,I
A
F
F
NOTE: The distance from a fanned draught
appliance terminal installed parallel to a
(mm)
boundary may not be less than 300mm in
accordance with the diagram below
300
150
200
200
150
Terminal
300
Assembly
300
600
1200
1200
1500
300
300
300
Top View Rear Flue
mm
300
300
1000
600
Fig. 16
3
/
in)
4
300 min
Property Boundary Line