Chapter IV Quick Installation Guide

This part mainly introduces quick installation of the equipment, according to the following
description, you could complete installation of the equipment in the shortest time, in the safest
way.
Note
Threaten brought by static electricity – Static electricity is a fatal threaten to electronic
equipment, for static electricity may puncture some electronic parts, causing failure of the whole
equipment, and bringing along huge losses unconsciously. So, during operation on equipment,
make sure to carry out electrostatic protection, which will not be noted in the following sections.

4.1 Cabinet preparation

Cabinet leveling: Cabinet must be placed firmly, adjust four legs at the bottom, make the cabinet
be placed on the ground firmly. Meanwhile, dismantle cabinet door and side panel
for guide rail installation.
Cabinet grounding: In order to avoid electric shock risk, it is required to install an earthing device
inside the cabinet. If power line of this equipment is inserted into power socket as
part of the cabinet, proper earthing must be provided for the cabinet. If power line
of storage system is inserted into power socket on the wall, earthing device inside
power socket only provides earthing for this equipment, it is required to provide
proper earthing protection for the cabinet as well as other equipment inside it. It is
suggested that you shall use the cabinet specially designed for Inspur storage system.
If you're using an Inspur storage cabinet, and all parts inside the cabinet are
grounded, Please do not change any of earthing connections inside the cabinet.
Temperature: If storage equipment is installed inside the cabinet, operating and working
temperature of storage system shall not be lower than 5 , nor higher than 35 .
Ventilation: Cabinet used by storage equipment shall provide sufficient wind flow for front and
rear parts of the system, and shall guarantee a 4100Btu heat discharge per hour,
while above 1m space shall also be kept in front and rear.

4.2 Storage system guide rail suite

Articles contained in guide rail suite for this equipment are as shown in Table 4-1.