Gas Supply Piping

Attention: Proper gas pressure is important but gas
volume is more critical than pressure. Right volume gas
supplies to system can be expect full performance. You
may calculate right gas pipe for right volume supply.
Check the rating plate to make sure that the unit was
built for the type of gas available in the area.
The gas supply piping should be sized according to the
Applicable Plumbing Code for a maximum draw of
185,000 BTUH. First determine the effective length of
the gas supply line by measuring the actual length of
piping, and then adding 5 ft. for every elbow or "T" to
the actual length. Use the charts below to determine
the pipe diameter necessary to accommodate the BTU
demand of the unit.
appliances on the line, size according to the maximum
amount of BTU demand.
The gas supply pressures must be within the ranges of
the following chart:
Natural Gas
Supply Pressure
Propane Gas
Supply Pressure
Pipe
Size
Length
10'
20'
½"
174
119
¾"
363
249
1"
684
470
1 ¼"
1404
965
1 ½"
2103
1445
2"
4050
2784
Pipe
Size
Length
10'
20'
½"
275
189
¾"
567
393
1"
1071
732
1 ¼"
2205
1496
1 ½"
3307
2299
2"
6221
4331
If there is more gas drawing
Min. 5" WC
Max. 10.5" WC
Min. 11" WC
Max. 14" WC
Natural Gas Supply Piping
Based on 0.60 specific gravity for natural gas at .5" WC pressure drop
DOE standard is 1100 BTU per cubic ft. of natural gas
30'
40'
50'
96
82
73
200
171
152
377
323
286
775
663
588
1161
993
880
2235
1913
1696
Propane Supply Piping
Based on 11" WC supply pressure
30'
40'
50'
152
129
114
315
267
237
590
504
448
1212
1039
913
1858
1559
1417
3465
2992
2646
Insufficient gas supply pressure can cause the Flash
Water Heater to lose efficiency or not work at all.
WARNING: Fire or explosion may result if the maximum
supply pressures are exceeded.
The manifold gas pressure should be at maximum 2.3"
WC for natural gas, and 2.5" WC for propane.
Always use approved connectors to connect the unit to
the gas line. Always purge the gas line of any debris
before connecting to the water heater.
WARNING: Conversion of this unit from natural gas to
propane or propane to natural gas cannot be done in
the field. Contact your local retailer or distributor to get
the correct unit for your gas type.
Always install a manual shutoff valve on the gas supply
line in case of an emergency, or if service or
maintenance is necessary.
This appliance and its individual shut-off valve must be
isolated from the gas supply piping system by
unplugging the unit and turning off the main gas valve
during any pressure testing of the gas supply piping
system at test pressures equal to or less than ½ PSI.
When all of the connections have been made, check
the gas line for leaks. Apply soapy water to all gas
fittings and connections, if bubbles form, there may be a
leak.
Cubic Feet of Natural Gas
60'
70'
80'
66
61
56
138
127
118
259
239
222
532
490
456
798
734
683
1536
1413
1315
kBTU of Propane
60'
70'
80'
103
96
89
217
196
185
409
378
346
834
771
724
1275
1181
1086
2394
2205
2047
90'
100'
125'
53
50
44
111
104
93
208
197
174
428
404
358
641
605
536
1234
1165
1033
90'
100'
125'
83
78
69
173
162
146
322
307
275
677
630
567
1023
976
866
1921
1811
1606
150'
200'
40
34
84
72
158
135
324
278
486
416
936
801
150'
200'
63
55
132
112
252
213
511
440
787
675
1496
1260