Battery Installation; Powering The Control Unit; Optional Modules; Check System Operation - Faraday MPC-6000 Installation, Operation And Maintenance Manual

Fire alarm system control unit
Table of Contents

Advertisement

MPC-6000 / MPC-7000 / RND-2 INSTALLATION, OPERATION AND MAINTENANCE MANUAL

Battery Installation

Improper battery connections or shorting battery terminals may damage the system
Use the battery calculation chart to determine the battery size. Place the batteries in the space
provided in the bottom of the backbox. If a battery set larger than12 AH (MPC-6000, RND-2) or
18 AH (MPC-7000) is required, a separate enclosure must be used. The Faraday 14050 may
be used for battery sets 18 AH and smaller. The Faraday BE-1 may be used for battery sets
38.5 AH up to 100 AH.
The control unit uses a 24V battery set. Connect the two 12V batteries (or four 6V batteries) in
series with wire that is rated for the maximum worst-case battery current draw. Route the
battery leads to the left of the enclosure and up to the battery connector, J4. The battery leads
are not power-limited. DO NOT CONNECT THE BATTERIES YET.

Powering the Control Unit

After all modules and wiring are installed and properly checked, apply AC power to the control
unit. AC POWER ON LED, SYSTEM TROUBLE LED, and the trouble buzzer should be on.
Observe polarity. Connect the B- (black) lead from the main board into the black or - terminal
of the battery set and the B+ (red) lead from the main board into the red or + terminal of the
battery set. (Refer to Primary and Secondary Wiring for diagram.)

Optional Modules

See Appendix D for the installation instructions for each optional module. Installation
Instructions are also provided with each module. Follow these instructions for proper
installation.
When using the MPC-DACT, select the proper System Type in the "System Parameter" tabs of
CIS-4. This automatically sets the "DACT Pwr Fail Tmr."

Check System Operation

Check for proper operation of all the system functions. See Operation Instructions section on
page 19.

WIRING

Basic system wiring and detector locations must be in accordance with NFPA 72 or other
instructions from the appropriate local authority having jurisdiction.
Devices that may be satisfactorily used with the control unit are shown in the compatible
device listing in Appendix B.
Wire reference data are included in Appendix A.
and/or batteries and may cause personal injuries.
Remote Station
Central Station
WARNING
15 Hours
6 Hours
36

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Rnd-2Mpc-7000

Table of Contents