Notification Appliance Circuits

The MPC-6000 control unit has four independent Class B (Style Y) notification appliance
circuits (NACs). Pairs of NACs can be combined for Class A (Style Z) operation. This reduces
the number of NACs to two. Each circuit can be selected to give continuous output or one of
eight sounding patterns available in the control unit including the Faraday SYNC Protocol.
There is also a system coder capable of zone-coded operation. All of the NACs are power
limited.

Serial Interface Circuit

The MPC-6000 control unit has a Serial Interface Circuit that will drive up to 16 remote LCD
annunciators and 8 Serial Relay Units and Serial Annunciator Units.

Status Relays

Four relays with dry contacts are provided. These relays are programmable to power fail,
alarm, trouble and supervisory functions. The relay contacts are Form C and are rated 1A @
28VDC resistive.

Programming Port

An RJ-11 jack is provided for a non-isolated RS-232 connection for temporary connection to a
computer for panel programming.