RDV4136 Series Direct Vent Gas Fireplace
Your fireplace is approved to be vented either through
the side wall, or vertically through the roof.
Only CFM Corporation venting components spe-
cifically approved and labelled for this fireplace
may be used.
Vent terminations shall not be recessed into a wall
or siding.
• Horizontal venting which incorporates the twist lock
pipe must be installed on a level plane without an
inclining or declining slope.
Horizontal venting which incorporates the use of flex
venting shall have an inclining slope from the unit of
1" (25 mm) per 24" (610 mm).
10
General Venting
There must not be any obstruction such as bushes,
garden sheds, fences, decks or utility buildings within
24" (610 mm) from the front of the termination hood.
Do not locate termination hood where excessive snow
or ice build up may occur. Be sure to check vent termi-
nation area after snow falls, and clear to prevent ac-
cidental blockage of venting system. When using snow
blowers, make sure snow is not directed towards vent
termination area.
Location of Vent Termination
It is imperative the vent termination be located observ-
ing the minimum clearances as shown on the next
page.
*Check with local codes or in absence of same with
CSA-B149.1 Installation Codes (1991) for Canada
or follow the current National Fuel Gas Code, ANSI
Z223.1/NFPA 54 for installations in the USA.