Bosch CE SPLIT series Installation And Maintenance Manual page 8

Table of Contents

Advertisement

8
CE Split Series
figure 7: Heater Package Compatibility
Model
Heater Model
ce025 thru 035
hp050-1Xs
ce049 thru 071
hp050-1XM
ce025 thru 035
hp075-1Xs
ce049 thru 071
hp075-1XM
ce025 thru 035
hp100-1Xs
ce049 thru 071
hp100-1XM
ce049 thru 071
hp150-1XM
hp150-1XM
ce049 thru 071
hp200-1XM
hp200-1XM
all heaters rated single phase 60 hz, and include unit fan load. all fuses type "d" time delay or hacR type breaker or
hRc FoRM 1. wire size based on 60 deg. c copper conductors.
Units supplied with internal electric heat
require two (2) separate power supplies: one
for the unit compressor and one for the electric
heater elements, blower motor and control
circuit. Refer to Figure #7 for wiring instruc-
tions, minimum circuit ampacities and maxi-
mum fuse/breaker sizing.
Connection point logic is as follows:
Table 1: Low Voltage Connection Points
function
from
Thermostat
24 hvac common
c
24 vac hot
R
Fan operation
g
Reversing valve (3)
o
1st stage
y1
compressor
operation
2nd stage
y2
compressor
operation
condensate
sensor (1)
alarm output
l
(From upM) (2)
auxilliary electric
w/w1/w2
heat (4)
emergency heat (4)
e
6 720 220 049
Kw
Heater amps
208v
240v
4.8
17.3
20.0
4.8
17.3
20.0
7.2
23.6
30.0
7.2
23.6
30.0
9.6
34.7
40.0
9.6
34.7
40.0
14.4
52.0
60.0
14.4
34.7
40.0
17.3
20.0
19.2
69.3
80.0
19.2
34.7
40.0
34.7
40.0
To air
from air
To
Handler
Handler
Condensing
Section
c1
c
c
R
R
R
g
o
o
o
y1
y1
y1
y2
y2
y2
cs
cs
splice
alR
w1
eM/w2
Subject to change without prior notice
Heater Package Compatibility
Circuit
MCa
208v
240v
l1/l2
27.1
30.4
l1/l2
27.1
30.4
l1/l2
34.9
42.9
l1/l2
35.7
43.8
l1/l2
48.8
55.4
l1/l2
49.5
56.3
single
71.2
81.3
l1/l2
49.5
56.3
l3/l4
21.7
25.0
single
92.9
106.3
l1/l2
49.5
56.3
l3/l4
43.4
50.0
TablE 1 noTES
1. For the condensate overflow sensor, connect
'CS' at the condensing section to 'CS' at the
air handler. Be sure to ground power supply.
2. If service LED is utilized connect 'ALR'
terminal on the UPM board to 'L ' on the
thermostat sub base. The wiring may be
spliced in the air handling unit. The 'ALR'
output is hot (R) so check thermostat
instruction manual to ensure compatibility.
3. 'O' – reversing valve is energized in the
cooling mode. Fail safe is to heating.
4. Utilized when electric strip heater
package present.
ECM InTErfaCE board
figure #8 - ECM Interface board
Max. fuse
awG
Min.
208v
240v
30
30
8
30
30
8
40
45
8
40
45
8
50
60
6
50
60
6
80
90
4
60
60
6
25
25
10
100
110
2
50
60
6
45
50
6
Revised 03-11