Sidewall Venting - Lochinvar GAS HEATER FOR COMMERICAL POOL Installation And Service Manual

Gas heaters for commercial pool applications 500,000 - 2,070,000 btu/hr models
Table of Contents

Advertisement

Installation and Service Manual
Figure 20 – Vertical DirectAire Installation with Rooftop
Combustion Air Inlet
Vent Kits
WARNING: Only use a sidewall air inlet cap
supplied by the appliance manufacturer or a
rooftop air inlet cap supplied by the vent
manufacturer. Using any other air inlet cap for
single-unit installations or using a common air
inlet cap for multiple units with insufficient free
area and/or protections from wind and weather
may result in operational problems and the
spillage of flue products. Spillage of flue
products can cause personal injury or death due
to carbon monoxide poisoning.
For single pool heater installations with sidewall air inlet, (see
Figure 18) you must order the sidewall air inlet kit. The part
number for each SVK kit is listed by input size in TABLE–D.
For single pool heater installations with rooftop air inlet (see
Figure 20), you must order the rooftop air inlet kit The part
number for each VDK kit is listed by input size in TABLE-D.
Purchase the flue pipe, rooftop flue termination, and air inlet
pipe locally.
There is no vent kit for combined air supply systems for multiple
pool heaters. Make sure the air inlet cap is properly sized. You
must purchase this cap locally.
Venting of Flue Products
For venting flue products vertically to the outdoors, follow all
requirements in the installation instructions for conventional
venting in this manual. Follow all clearance requirements in
Vertical Vent Termination Clearances and Location, page 10.
A barometric damper is not required in the flue on Vertical
DirectAire™ installations if the draft is within the negative
0.04 to 0.08 inches w.c. required for proper operation. If the
draft exceeds this range, install a barometric damper.
TABLE-D
DirectAire™ Kits
Input
Horizontal
Btu/hr
500,000
SVK3047
650,000
SVK3048
750,000
SVK3048
990,000
SVK3040
1,260,000
SVK3041
1,440,000
SVK3041
1,800,000
SVK3041
2,070,000
SVK3041
*
The SVK kits include a DV box adapter and sidewall air inlet cap. The
VDK kits include a DV box adapter and a rooftop air inlet cap. See note on
page 12 concerning DV box adapter.

3. Sidewall Venting

IMPORTANT: Before installing a venting system,
follow all venting clearances and requirements
found in the Venting, General Information
section, page 10.
This option uses a powered vent assembly which pulls the flue
products out of the stack. This fan generates a negative draft at
the pool heater. Combustion air is drawn from the mechanical
room (see Combustion and Ventilation Air, page 7).
Figure 21 – Sidewall Venting Installation with an Induced
Draft Fan and Sidewall Vent Cap
17
Vertical
Kit*
Kit*
VDK3026
VDK3027
VDK3027
VDK3023
VDK3024
VDK3024
VDK3024
VDK3024
T–C