Lochinvar GAS HEATER FOR COMMERICAL POOL Installation And Service Manual page 59

Gas heaters for commercial pool applications 500,000 - 2,070,000 btu/hr models
Table of Contents

Advertisement

Installation and Service Manual
Appendix B
Adjust Menu Settings for Operating Modes
User
Advanced
X
X
X
X
X
X
X(*)
X(*)
X
X
X
X
X
User Settings: Rear dip switch set to "1" position.
Advanced Settings: Rear dip switch set to "0" position.
(*) If equipped with optional pool supply sensor.
View Menu Item
Current Temperature
TARGET Set point
BOIL IN
BOIL OUT
BOIL ΔT
SUP (If equipped pool supply sensor)
BOIL ON (Advanced switch set to "0")
Advanced settings:
By pressing the Select key in the View mode while viewing the
Boiler ΔT reading (or the Supply Sensor temperature if the
Pool Supply sensor is connected), the Boiler On hours will be
displayed, indicated by the text BOIL ON in the display. This
is the total number of hours the pool heater has been heating
the pool.
By pressing the Select key in the Adjust mode while viewing
the Pool DIFF setting, the Boiler Inlet Minimum setting will be
displayed, indicated by the text BOIL IN MIN in the display.
The control will adjust the position of the 3-way automatic
bypass valve in order to maintain the inlet temperature at this
setting. The default is 130°F.
By pressing the Select key again, the Boiler Maximum setting
will be displayed, indicated by the text BOIL MAX in the
display. The control will shut off the heater whenever the
outlet temperature from the heater exceeds this setting. The
default value is 200°F.
If a Pool Supply sensor is connected, then by pressing the
Select key again, the Supply Target setting will be displayed,
indicated by the text SUP TARGET in the display. The
Item
Description
TARGET
Pool target temperature
DIFF
Differential setting for return sensor
BOIL IN MIN
Minimum inlet water temperature
BOIL MAX
Maximum outlet temperature
SUP TARGET
Supply water temperature
SUP DIFF
Differential setting for supply sensor
MOTOR SPEED
Setting other than 20 may void warranty
DLY
Time at which purging stops
BOIL ON
*Accumulated runtime of unit
F/C Units
Set temperature at °F or °C
View Menu Information
Menu Description
Pool return sensor temperature
Pool temperature set point
Inlet sensor temperature
Outlet sensor temperature
Heater differential temperature
Pool supply sensor temperature
Accumulated runtime hours
control will shut off the heater whenever the pool supply
temperature exceeds this setting. The default value is 100°F.
If a Pool Supply sensor is connected, then by pressing the
Select key again, the Supply Differential setting will be
displayed, indicated by the text SUP DIFF in the display.
After the control has turned off the heater because the pool
supply temperature exceeded the Pool Supply setting, the pool
supply temperature must drop by this amount before the
control will allow the heater to start up again. The default
value is 20°F.
By pressing the Select key again, the Valve Speed setting will
be displayed, indicated by the arrow pointing to the text
SPEED on the overlay. This setting is used to control the
responsiveness of the 3-way automatic bypass valve, and
should only be adjusted under the direction of Lochinvar's
Technical Services personnel.
seconds.
By pressing the Select key again, the pump Delay setting is
displayed, indicated by the DLY on the display. This is the
time that the heater pump will continue to run after the control
turns the heater off. The default value is 20 minutes.
59
Default
Range
85°F
OFF, 55 to 105°F
4°F
1 to 20°F
130°F
130 to 150°F
200°F
120 to 200°F
100°F
OFF, 70 to 110°F
20°F
2 to 20°F
20 sec
15 to 30 sec
20 sec
ON, 0:20 to 9:55 min
0 hr
0 to 999 hr
°F
°C or °F
The default setting is 20