Corrective Action - Lochinvar Armor 150 - 500 Service Manual

Lochinvar condensing water heater service manual
Table of Contents

Advertisement

3
Troubleshooting
Table 3E (continued from previous page) Troubleshooting Chart - Fault Messages Displayed on Water Heater Interface
FAULT
The unit was running and lost the flame
signal.
straight times.
Exception: The 500 Model will lock out after
one (1) try.
No Flame
Running
(will require a manual
reset once the condition
has been corrected.
Press the RESET button
on the SMART
SYSTEM display to
reset.)
(continued)
DESCRIPTION
This condition occurred four (4)

CORRECTIVE ACTION

• Inspect spark electrode and associated wiring for
damage and connection. Reference page 19 of this
manual for removal and cleaning procedures. Replace
if necessary.
• Check for proper electrical grounding of unit.
• Check incoming supply gas pressure.
pressures should be between 4 - 14 inches w.c. and
LP gas pressures should be between 8 - 14 inches w.c.
Refer to Section 7 - Gas Connections of the Armor
Water Heater Installation and Operation Manual for
detailed information concerning the gas supply.
• Verify that the plastic hose from the gas valve to the air
inlet is connected and is not damaged.
• Verify that the vent/air intake pipes are installed
correctly and there are no obstructions.
• Check for 24 VAC to the gas valve at the 2-pin
connection on the side of the main control board during
the ignition attempt. If no voltage is present, replace the
main control board.
• If 24 VAC is present at the main control board, check
the wiring between the main control board and the gas
valve.
Replace the wiring if necessary.
disconnect the wiring from the gas valve and attempt to
measure voltage at that point. The main control board
can detect if the gas valve is not connected and will
display the GV / Relay Fail fault.
• If 24 VAC is present, check the outlet of the valve to
ensure the valve is flowing gas. With a manometer
connected to the outlet tap of the gas valve, when the
unit is in the prepurge period, there should be a
negative pressure present.
energized a change in pressure should occur. If the
pressure change does not occur, the gas valve is not
opening. Replace the gas valve.
• Inspect
flame
sensor
Reference page 19 of this manual for removal and
cleaning procedures. Replace if necessary.
• Inspect the burner. Reference page 19 of this manual
for removal and cleaning procedures.
necessary.
• Replace the main control board.
Service Manual
Natural gas
Do not
When the valve is
and
associated
wiring.
Replace if
27

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Armor 150Armor 500

Table of Contents