installing
Place the stove on a noncombustible type floor or floor protector
that extends a minimum of 6 inches (152mm) to the front of the load
door opening, 6 inches (152mm) to the sides of the door opening,
and 6 inches to the rear. Floor protection must also extend 2 inches
(51mm) beyond each side of any horizontal flue pipe. The minimum
floor protector material is 20 gauge sheet metal. Other floor protector
materials are ceramic tile, stone, brick, etc.
nOte for canadian installation only: Per ULC-S627-00, If installed
on a combustible floor, the need to provide a noncombustible floor
protector covering the area beneath the space heater and extending
at least 17.72" (450mm) on the firing side and at least 7.87" (200mm)
on the other sides.
In Canada, you may follow smaller U.S. floor protection
requirements OnlY if the user agrees to completely shut-
down the appliance, and allow it to cool to where all fire is
extinguished and the combustion blower and its indicator
light shuts off, prior to opening the firebox door or ash door.
Place the stove away from combustible walls at least as far as
shown in Figures 3 and 4. Please note the difference in side wall
clearance with and without side shields.
Note that the clearances shown are minimum for safety but do not
leave much room for access when cleaning or servicing. Please
take this into account when placing the stove.
Connect the power cord to a 120 V.A.C. 60Hz grounded receptacle.
(A surge protector is recommended to protect the circuit board.)
Also be sure that the polarity of the outlet that the stove is plugged
into is correct.
Prior to installing the flue pipe, connect a draft meter. (The draft
meter must have a minimum range of 0 - .5") Record the first reading.
Connect flue pipe to stove and be sure all doors and windows in the
home are closed. Record the second draft reading_______. If the
second reading is more than .05" lower than the first reading, check
for possible restrictions or the need for outside air (see page 10).
For more information on the draft test procedure, refer to Page 21.
Mobile home installation
When installing this unit in a mobile home, several requirements
must be followed:
1. The unit must be bolted to the floor. This can be done with 1/4"
lag screws through the 2 holes in the base plate.
2. The unit must also be connected to outside air. See page 10.
3. Floor protection and clearances must be followed as shown.
4. Unit must be grounded to the metal frame of the mobile home.
cautiOn: this appliance must be vented to the outside.
Due to high temperatures, the stove should be placed out of traffic
and away from furniture and draperies.
Children and adults should be alerted to the hazards of high surface
temperatures and should stay away to avoid burns to skin and/or
clothing.
Young children should be carefully supervised when they are in the
same room as the stove.
Clothing and other flammable materials should not be placed on
or near this unit.
waRning
the StRuctuRal integRitY OF the
ManuFactuRed hOMe FlOOR, wall, and
ceiling/ROOF MuSt be Maintained.
dO nOt inStall in SleePing ROOM.
3-90-04301R14_09/12
installation
9"(228mm)With or Without Side Shields
10" (254mm) with
side shields
16" (406mm)
without side shields
Minimum Size floor protection (USA) is 32
33" deep (825mm X 838mm).
* Floor protection dimensions for the front and sides
are measured from the appliance door opening in
The United States. In Canada, the side dimension is
measured from the widest part of the appliance.
Floor Protection
Requirements
j
k
l
nOte:
Measurement "L"
is measured from
the pedestal base
in the US ONLY
nOte:
Measurement "K"
is measured from
the glass in the
US ONLY
9"(228mm)
Fig. 3
Fig. 3
10" (254mm)
16" (406-mm)
36"(914mm)
Fig. 4
US
Sides
6"
Front
6"
Rear
6"
j
k
uSa
F
loor protector
P43 Pellet Stove
2"(51mm)
" wide By
1/2
Canada
200mm
450mm
200mm
l
j
canada
7