DIAGNOSTICS
A spanner symbol and LCD fault code will appear automatically if there is a fault in the temperature
measuring system, defrost system, fans or low ambient heater. (Refer diagram below.)
When the PC door is opened, an alarm will sound. The number of beeps also indicates the fault
code. Pressing any of the control buttons can deactivate these alarms.
Example: When a fault develops, the LCD fault code appears with the spanner.
After rectifying the problem, the fault code and spanner will disappear. Faults are only rectified
when that feature is used. So in the case of a defrost fault, the code will remain until a defrost is
initiated and it is successful.
5.1
Fault Codes
Fault Code 1
Reason:
On the last power up, the power module failed self-test.
Primary Action:
Fault Code 2
Reason:
Primary Action:
Fault Code 3
Reason:
Primary Action:
Secondary Action:
Tertiary Action:
Fault Code 4
Reason:
Primary Action:
Secondary Action:
Tertiary Action:
Fault Code 5
Reason:
Primary Action:
Secondary Action:
Fault Code 6
Reason:
Primary Action:
Secondary Action:
Replace the power module.
The previous 2 defrosts were aborted after 40 minutes.
Check the defrost element assembly in the FC. If faulty, replace.
The resistance of all the temperature sensors are outside the normal range.
(> 45K Ohms)
Check the 6-way RAST connector at the power module.
Re-terminate the 6-way RAST connector.
Replace the power module.
The resistance of all the temperature sensors are outside the normal range.
(< 660 Ohms)
Check the 6-way RAST connector at the power module.
Re-terminate the 6-way RAST connector.
Replace the power module.
The resistance of the FC sensor is outside the normal range (> 45K Ohms).
Check the sensor connection at the power module.
Replace the sensor.
The resistance of the FC sensor is outside the normal range (<660 Ohms).
Check the sensor connection at the power module.
Replace the sensor.