24 | Fan Motor Options
Table 5: PSC Motor Performance Data
Rated
Fan
Model
Airflow
Speed
Low
SV-041
Med
Hi
1200
Low
SV-042
Med
Hi
1400
Low
SV-048
Med
Hi
1600
Low
SV-060
Med
Hi
2000
Low
SV-070
Med
Hi
2100
Note: 575V models employ 1 speed motors (high only)
8 733 914 818 (2014?08)
0.10
0.20
0.30
0.40
990
990
970
950
1220
1190
1150
1120
1450
1380
1320
1250
1210
1210
1190
1160
1460
1450
1430
1390
1750
1710
1670
1620
1450
1440
1420
1400
1700
1670
1630
1580
1930
1870
1810
1740
1560
1550
1540
1530
1890
1880
1870
1860
2220
2200
2150
2100
1570
1560
1550
1540
1900
1890
1880
1870
2240
2220
2200
2150
Subject to change without prior notice
0.50
0.60
0.70
0.80
920
860
-
-
1080
1020
940
-
1190
1120
1040
960
1120
1080
-
-
1330
1250
1160
-
1560
1460
1330
1210
1360
1320
-
-
1530
1470
1400
-
1670
1600
1520
1430
1505
1475
1440
1400
1825
1790
1730
1670
2050
2000
1940
1870
1530
1505
1475
1440
1860
1825
1790
1730
2100
2050
2000
1940

Constant Torque Motors (ECM)

For installations where the efficiency of an
electronically commutated brushless DC motor
(ECM) motor is required, but the features of a
constant airflow motor are not required, the SV
series is offered with a constant torque ECM motor
option. These motors feature up to 90% thermal
efficiency combined with a flatter fan curve than a
PSC motor and simple operation. These motors
are provided with 5 speed taps to allow for a wide
range of air flow and external static options. To
change a speed tap follow the instructions below:
1. Disconnect power to the heat pump.
2. Remove the blower access panel.
3. Remove the speed tap wire from the terminal it
is currently connected to and connect it to the
terminal desired.
Refer to the constant torque motor performance
tables for heat pump blower performance with the
constant torque motor option.
SV Heat PumpSeries
0.90
1.00
1.10
1.20
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
1080
-
-
-
-
-
-
-
-
-
-
-
1340
-
-
-
-
-
-
-
1590
1500
-
-
1800
1700
1590
-
1400
-
-
-
1670
1590
1500
-
1870
1800
1700
1590
SV Heat Pump Series

Hide quick links:

Advertisement

Table of Contents
loading