Daewoo DTB-F071LH-DVI Service Manual page 18

Table of Contents

Advertisement

7.9 Outdoor unit LED display function:
1. When stand-by it display number of indoor unit online;
2. When operation it display frequency of outdoor unit;
3. When defrost it display "df";
4. When a protection or error occurred, it display as the following table:
Display
E0
EEPROM error
E1
No 1 Indoor units pipe temp. sensor or connector of pipe temp. sensor is defective
E2
No 2 Indoor units pipe temp. sensor or connector of pipe temp. sensor is defective
E3
No 3 Indoor units pipe temp. sensor or connector of pipe temp. sensor is defective
E4
Outdoor temp. sensor or connector of temp. sensor is defective
E5
Compressor voltage protection
E6
No 4 Indoor units pipe temp. sensor or connector of pipe temp. sensor is defective
E7
Indoor and outdoor communication error
P0
Compressor top protection against temperature
P1
High pressure protection
P2
Low pressure protection
P3
Compressor current protection
P4
Inverter module protection
P5
Outdoor low temp. protection
P6
Condenser high-temperature protection
7.10 Check function:
There is a check button on outdoor pcb. When push this button, the outdoor LED can display
in sequence:
Capacity demand→Running mode →revised capacity → fan state →No.1 evaporator pipe
temp. →No.2 evaporator pipe temp.→No.3 evaporator pipe temp.→No.4 evaporator pipe
temp.→outdoor pipe temp. → Outdoor temp. →discharge gas temp.→current of outdoor unit
→ No. 1 opening degree of electronic expansion valve → No. 2 opening degree of EXV →
No. 3 opening degree of EXV→No. 4 opening degree of EXV→indoor unit number→last
protection/error code→capacity demand(cycle)
Explanation for the some display content:
1. Running mode:
Display
Corresponding mode
0
Off
1
Cooling mode
2
Heating mode
Explanation

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents