Premier 2-zone controller
Hide thumbs Also See for 140202:

Advertisement

[
]
Verify green heartbeat LED in middle of panel is pulsing.
[
]
Verify zone LEDs near damper terminals are green.
[
]
Switch zone 1 thermostat to heat mode, and call for heat in zone 1 by raising set
temperature above room temperature.
[
]
Verify zone 1 damper LED stays green (open) and zone 2 damper LED changes to red
(closed).
[
]
Verify heating system is operating, air is moving out zone 1 vents, and zone 2 vents have
minimal airflow.
[
]
Switch zone 2 thermostat to heat mode, and call for heat in zone 2 by raising set
temperature above room temperature.
[
]
Verify zone 1 damper LED stays green (open) and zone 2 damper LED changes to
green (open).
[
]
Verify heating system is operating and air is moving out into zone 1 and zone 2.
[
]
If installed, verify emergency heat remote and panel switch. Return E-Heat switches to
normal position when test is complete.
[
]
Return zone 1 thermostat to the off position. Verify zone 1 damper LED turns red and
zone 2 damper LED stays green.
[
]
Verify heating system is operating, air is moving out zone 2 vents, and zone 1 vents have
minimal airflow.
[
]
Return zone 2 thermostat to the off position. Verify system fan shuts off at the end of
90-second purge cycle.
[
]
Verify zone LEDs near damper terminals are green.
[
]
If the outside temperature is acceptable, repeat the above steps in cooling mode.
Cooling will not work if E-Heat is on.
[
]
Restore thermostats and replace J2 jumper if short cycle protection at zone panel
is required.