Premier 2-zone controller
Hide thumbs Also See for 140202:

Advertisement

3.2
Thermostat Wiring
Install the system thermostats using the instructions
provided by the manufacturer.
Connect the thermostats to the zone panel as shown.
Notes:
• Wiring to the C terminal is required only for
thermostat power.
• E terminal at thermostat 1 controls emergency heat.
See E-Heat Switch Installation Sheet TSB-0708-01
for wiring details.
3.3
Transformer Wiring
Install the transformer using the instructions provided
by the manufacturer. Size the transformer to the damper
requirements. The zone panel has a built-in, self-resetting
fuse. The maximum damper power per panel is 35 VA at
24 VAC.
Connect the transformer to the zone panel as shown.
Note: Additional dampers or dampers with a higher current draw will require the use of a separate
slave relay.
Rh
Rc
Y
G
W
C
Thermostat
HOT
C
Dedicated
Zoning Transformer
4
E
R
Y
G
W
C
Zone Panel
24V
24C
C
Zone
Panel