25 electrolux electrical work
Caution
After the confirmation of the above conditions, prepare the wiring as follows:
1. Never fail to have an individual power circuit specifically for the air
conditioner. As for the method of wiring, be guided by the circuit diagram
posted on the inside of control cover.
2. The screw which fasten the wiring in the casing of electrical fittings are
liable to come loose from vibrations to which the unit is subjected during
the course of transportation. Check them and make sure that they are all
tightly fastened. (If they are loose, it could cause burn-out of the wires.)
3. Specification of power source.
4. Confirm that electrical capacity is sufficient.
5. See to that the starting voltage is maintained at more than 90 percent of the
rated voltage marked on the name plate.
6. Confirm that the cable thickness is as specified in the power source
specification.
7. Always install an earth leakage circuit breaker in a wet or moist area.
8. The following would be caused by voltage drop. Vibration of a magnetic
switch, which will damage the contact point, fuse breaking, disturbance of
the normal function of the overload.
9. The means for disconnection from a power supply shall be incorporated in
the fixed wiring and have an air gap contact separation of at least 3mm in
each active (phase) conductors.

Air purging

Air and moisture in the refrigerant system have undesirable effects as
indicated below:
1. Pressure in the system rises.
2. Operating current rises.
3. Cooling or heating efficiency
drops.
4. Moisture in the refrigerant circuit
may freeze and block capillary
tubing.
5. Water may lead to corrosion of
parts in the refrigeration system.
6. Therefore, the indoor unit and
tubing between the indoor and
outdoor unit must be leak tested
and evacuated to remove any
noncondensables and moisture
from the system.
Air purging with vacuum pump
1. Check that each tube(both liquid and gas side tubes) between the indoor
and outdoor units have been properly connected and all wiring for the test
run has been completed. Remove the service valve caps from both the gas
and the liquid side on the outdoor unit. Note that both the liquid and the gas
side service valves on the outdoor unit are kept closed at this stage.
2. When relocate the unit to another place, perform evacuation using vacuum
pump.
3. Pipe length and refrigerant amount:
Air purging
Connective
metod
pipe length
Less than 5 m
Use vacuum pump.
More than 5m
Use vacuum pump.
Caution in handling the packed valve
1. Open the valve stem until it hits against the stopper. Do not try to open it
further.
2. Securely tighten the valve stem cap with a spanner or the like. Valve stem
cap tightening torque (See Tightening torque table in page 19).
Refrigerant
Outdoor unit
Indoor unit
Gas
A
C
D
B
Packed valve
Half union
electrical work electrolux 26
Additional amount of
refrigerant to be charged
Liquid side:φ6.35mm
Liquid side:φ9.52mm:
R410A: (Pipe length-5)x20g/m
R410A: (Pipe length-5)x40g/m
Flare nut
Valve body
Valve stem
Stopper
Cap