High Temperature And Overload Protection Diagnosis - Gree GWC09QB-K3DNB2B Service Manual

Refrigerant r410a
Table of Contents

Advertisement

Service Manual
3. High temperature and overload protection diagnosis (AP1 hereinafter refers to the control board of the outdoor
unit)
Mainly detect:
Installation and Maintenance
Overheat and high
temperature protection
Is outdoor ambient temperature higher than 53?
N
20 minutes after the complete
unit is powered off.
Is heat dissipation of the indoor unit
and outdoor unit abnormal?
N
Does the outdoor fan work normally?
Y
Replace the
control panel
AP1
End
Normal protection, please operate
it after the outdoor ambient temp-
Y
erature is normalized.
Improve the heat
Y
dissipation environ-
ment of the unit
1. Check if the fan terminal OFAN
is connected correctly
2. Resistance between any two
N
terminals is measure by an ohm
gauge and should be less than 1K
Ohm.
Replace the fan
capacitor C1
Replace the
outdoor fan
53