Operation Characteristics - Interlogix 600-6520-95 Manual

Carbon monoxide alarm
Table of Contents

Advertisement

Operation characteristics

Table 2: Operation characteristics
LED Display
Normal operation
Green Power
LED flashes
every 30
seconds.
Carbon monoxide
Red Alarm LED
alarm
flashes with
beeps.
Low battery /
Red Alarm LED
low battery hush
flashes every
60 seconds.
Alarm end-of-life
Red Alarm LED
indicator
flashes two
times every 30
seconds.
Trouble/service
Red Alarm LED
alarm
flashes every
30 seconds.
Error condition
Red Alarm LED
constantly on.
Test mode
Red Alarm LED
flashes with
beeps.
a
Tamper
Red Alarm LED
flashes every
30 seconds.
a. Local indication starts 3.5 minutes after the unit is removed from the mounting plate.
466-2411 REV A May 2011
Alarm sound
Unit status
None.
Normal DC
operation (sensing
no CO) and with
good batteries.
Four quick beeps,
Alarm condition.
5 seconds
Dangerous
silence,
concentrations of
repeating.
CO detected.
One quick beep
Batteries need to be
every 60
replaced.
seconds.
Two quick beeps
End of CO alarm
every 30
life.
seconds.
One quick beep
Unit is in trouble
every 30
condition.
seconds.
Constant alarm.
Very low battery or
unit malfunction.
Four quick beeps,
Normal operation
5 seconds
when Test/Hush
silence, repeated
button is pressed.
once.
One quick beep
Unit is in tamper
every 30
condition.
seconds.
Control panel status
Recommendation
Normal operating
None.
condition.
Alarm condition.
See "Alarm procedure" on page 8.
Trouble condition,
Replace all three AA batteries.
trouble beeps every 60
Press Test/Hush button and release.
seconds.
This will silence the low battery audible
chirp between 8 and 11 hours allowing
for a more convenient time to replace
the batteries.
Not applicable.
Press the Test/Hush button and
End-of-life events are
release. This will silence the end-of-life
not communicated to
signal for up to three days. After three
the control panel.
days, the unit will resume end-of-life
chirps. Hush mode will silence the
alarm ten times or up to 30 days. After
30 days, the unit can no longer be
hushed. Replace the CO alarm
immediately. The unit will not respond
to CO.
Not applicable.
Replace batteries. If condition
Trouble/Service events
continues, unit has malfunctioned.
are not communicated
Replace immediately. Unit will not
to the control panel.
respond to CO.
Not applicable.
Replace batteries. If condition
Error conditions are
continues, unit has malfunctioned.
not communicated to
Replace immediately. Unit will not
the control panel.
respond to CO.
Sensor test mode
CO not detected. Alarm for test
purposes only.
Not applicable.
Place alarm body back onto mounting
Tamper events are not
plate. If condition continues, unit has
communicated to the
malfunctioned. Replace immediately.
control panel.