Solenoid Valves (Sva, Svb, Svc, Svm); Bc Controller Transformer - Mitsubishi Electric PUHY-200YMF-C Service Handbook

Air conditioners city multi
Table of Contents

Advertisement

Solenoid valves (SVA, SVB, SVC, SVM)

Coordination signals output from the board and solenoid valve operations.
Note 1 : (SVA, SVB, SVC)
SVA, SVB and SVC are turned on and off in accordance with operation mode.
Mode
Branch port
SVA
SVB
SVC
(SVM)
SVM is turned on and off in accordance with operation mode.
Operation Mode
Cooling-only
SVM
Note 2 : (SVA, SVB, SVC)
Measure temperature of piping on either side of SVA 1-A
Measure temperature of piping on either side of SVB 1-B

4) BC controller transformer

BC Controller control board
CNTR
Red
Blue
Cooling
Heating
ON
OFF
OFF
ON
ON
OFF
Cooling-principal
Heating-only Heating-principal
ON
OFF
B
A
1
CN03
Brown
Brown
*SVM is not built in depending on models.
Stopped
OFF
OFF
OFF
Defrosting
OFF
OFF
(SVM)
Measure temperature at points marked "X".
CMB-P-V-E
CNTR(1)-(3)
Approximately 90Ω
CN03(1)-(3)
Approximately 1.7Ω
* Disconnect the connector before measurement.
–112–
Defrosting
OFF
OFF
OFF
Stopped
ON
OFF
Normal
Malfunction
Open or shorted

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents