Mitsubishi Electric PUHY-200YMF-C Service Handbook page 154

Air conditioners city multi
Table of Contents

Advertisement

No
SW1
Item
12345678910
21
1010100000
Outdoor Unit
Preliminary Error
History
22
0110100000
23
1110100000
24
0001100000
25
1001100000
Error History 1
0101100000
Inverter Error Detail
26
27
1101100000
Error History 2
28
0011100000
Inverter Error Detail
29
1011100000
Error History 3
30
0111100000
Inverter Error Detail
31
1111100000
Error History 4
32
0000010000
Inverter Error Detail
33
1000010000
Error History 5
34
0100010000
Inverter Error Detail
35
1100010000
Error History 6
36
0010010000
Inverter Error Detail
37
1010010000
Error History 7
38
0110010000
Inverter Error Detail
1110010000
Error History 8
39
0001010000
Inverter Error Detail
40
1001010000
Error History 9
41
42
0101010000
Inverter Error Detail
43
1101010000
Error History 10
44
0011010000
Inverter Error Detail
45
1011010000
Type of Inverter Error
Preliminary (Details
of the inverter error in
No. 17)
46
0111010000
TH1 Data
47
1111010000
TH2 Data
48
0000110000
LD1 Data
49
1000110000
LD2 Data
50
0100110000
TH5 Data
51
1100110000
TH6 Data
LD1
LD2
LD3
High
Low
Discharge
Overcur-
Pressure
Pressure
Tempera-
rent
Error 1, 2
Error
ture Error
Protection
Suction
Configuration
Comp.
pressure
Detection
tempera-
Error
Error
ture Error
TH1
TH2
LD1
LD2
Error
Error
Error
Error
TH7
TH9
TH10
Error
Error
Error
Inverter Error Detail (1 ~ 13)
Inverter Error Detail (1 ~ 13)
Inverter Error Detail (1 ~ 13)
Inverter Error Detail (1 ~ 13)
Inverter Error Detail (1 ~ 13)
Inverter Error Detail (1 ~ 13)
Inverter Error Detail (1 ~ 13)
Inverter Error Detail (1 ~ 13)
Inverter Error Detail (1 ~ 13)
Inverter Error Detail (1 ~ 13)
0 : OFF 1 : ON 2 : OPEN
0 : OFF 1 : ON 2 : OPEN
–153–
Display
LD4
LD5
LD6
LD7
Heat Sink
Overcur-
Thermostat
rent
Operation
Break
TH5
TH6
HPS
Error
Error
Error
0 ~ 9999
0 ~ 9999
0 ~ 9999
0 ~ 9999
0 ~ 9999
0 ~ 9999
0 ~ 9999
0 ~ 9999
0 ~ 9999
0 ~ 9999
0 ~ 9999
-99.9 ~ 999.9
-99.9 ~ 999.9
for PURY-(P)200·250YMF-C
Remarks
LD8
Over-
Lights up if an error
charged
delay has occurred
Refrigerant
between the time the
power was turned on
and the present time.
To turn the indicators
off, switch the power
OFF briefly.
THHS
E*
Error
The error and error
delay code are
displayed. If the
address and error
code are shown in
reverse, or there is
no error, "- - - -" is
displayed. E
If there is no error, "-
- - -" is displayed. E
E
If there is no error,
"- - - - " is always
overwritten.
E*
No. 52 THHS
data are
monitored by
the inverter
microcomputer.
E*