Thermal Sensor Abnormality (Outdoor Unit); Cooling Fan Abnormality - Mitsubishi Electric PUHY-200YMF-C Service Handbook

Air conditioners city multi
Table of Contents

Advertisement

Checking code
Meaning, detecting method
4260
Cooling fan
If the heat sink temperature (THHS)
abnormality
100°C for 20 minutes or longer just
before the inverter starts.
5101
Discharge
<Other than THHS>
1 A short in the thermistor or an
(TH1)
open circuit was sensed. The
5102
Low
outdoor unit switches to the
pressure
temporary stop mode with re-
saturation
starting after 3 minutes, then if
(TH2)
the temperature detected by the
thermistor just before restarting
5103
Detected switch
is in the normal range, restart-
liquid level
ing takes place.
(LD1)
2 If a short or open circuit in the
thermistor is detected just be-
5104
Detected switch
fore restar ting, error code
liquid level
"5101", "5102", "5103", "5104",
(LD2)
"5105", "5106", "5108", "5109"
or "5112" is displayed.
3 In the 3 minute restart mode,
5105
Heat
exchanger
the abnormal stop delay LED is
inlet pipe
displayed.
4 The above short or open circuit
(TH5)
is not detected for 10 minutes
5106
Ambient
after the compressor starts, or
tempera-
for 3 minutes during defrosting
ture (TH6)
or after recovery following de-
frosting.
5107
Heat
<THHS>
exchanger
If a heat sink (THHS) temperature
outlet pipe
of
-40°C is detected just after the
(TH7)
inverter starts or during inverter
operation.
5108
SC coil
bypass
outlet
(TH8)
5109
CS circuit
(TH9)
5110
Radiator
panel
(TH HS)
5112
Compres-
sor shell
tempera-
ture
(TH10)
* TH2, TH9, TH10 : P-YMF-B only
5111
1. When short (high temp. inlet) or
open (low temperature inlet) of
Liquid inlet
thermistor is detected during
(TH11)
operation, error stop will be
commenced displaying "5111"
or "5112", "5113" or "5114", or
"5115" or "5116.
2. The above detectection is not
Bypass
made during defrostig and 3-
outlet
minute after changing operation
(TH12)
mode.
Bypass
inlet
(TH15)
Intermedi-
ate section
(TH16)
Cause
1) Same as "4230."
1) Thermistor
2) Lead wires are being pinched.
3) Insulation is torn.
4) A connector pin is missing, or there
is faulty contact.
5) A wire is disconnected.
6) The thermistor input circuit on the
MAIN circuit board is faulty.
(In the case of the THHS, replace
the INV board.)
Short Circuit Detection
TH1
240°C or higher (0.57 kΩ )
TH2
70°C or higher (1.71 kΩ )
LD1
LD2
TH5
110°C or higher (0.4 kΩ )
TH6
110°C or higher (0.4 kΩ )
TH7
110°C or higher (1.14 kΩ )
TH8
70˚C or higher (1.14 kΩ )
TH9
70°C or higher (1.14 kΩ )
THHS
TH10
240°C or higher (0.57 kΩ )
1) Thermistor trouble.
2) Biting of lead wire.
3) Broken cover.
4) Coming off of pin at connector por-
tion, poor contact.
5) Broken wire.
6) Faulty thermistor input circuit of
control board.
Short Detected
TH11
110°C or more (0.4 kΩ )
TH12
110°C or more (0.4 kΩ )
TH15
70°C or more (1.14 kΩ )
TH16
70°C or more (0.4 kΩ )
–130–
Checking method & Countermeasure
Same as "4230."
Check the thermistor's resistance.
Check if the lead wires are pinched.
Check for tearing of the insulation.
Check if a pin is missing on the con-
nector.
Check if a wire is disconnected.
Check the temperature picked up by
the sensor using the LED monitor.
If the deviation from the actual tem-
perature is great, replace the MAIN cir-
cuit board.
(In the case of the THHS, replace the
INV board.)
Open Circuit Detection
15°C or lower (321 kΩ )
-40°C or lower (130 kΩ )
-40°C or lower (130 kΩ )
-40°C or lower (130 kΩ )
-40°C or lower (130 kΩ )
-40°C or lower (130 kΩ )
-40°C or lower (130 kΩ )
-40°C or lower (130 kΩ )
-40°C or lower (130 kΩ )
-40°C or lower (2.5 MΩ )
-15°C or lower (1656 kΩ )
Check thermistor resistance.
Check lead wire biting.
Check broken cover.
Check coming off of pin at connector.
Check broken wire.
Check sensor sensing temperature. If
it deviates from the actual temerature
seriously, replace control panel.
Open Detected
-40°C or less (130 kΩ )
-40°C or less (130 kΩ )
-40°C or less (130 kΩ )
-40°C or less (130 kΩ )