ECONCEPT 100
Positioning the external sensor
The external sensor should preferably be installed on the North, North-West wall or on the wall with most
of the main living room. The sensor must never be exposed to early morning sunshine and in general, as far
as possible, it must not be hit directly by the sun's rays; if necessary, it should be protected.
In any case, the sensor must never be fitted near windows, doors, ventilation openings, flues or sources of
heat that could affect the reading.
Note: The maximum permissible length of the electric cable connecting the boiler - external sensor is
50 m. A common 2-wire cable can be used.
Fig. 10
N
N W
15