5-4. FIXING HORIZONTAL VANE
Horizontal vane of each air outlet can be fixed according to the environment where it is installed.
Setting procedure
1) Turn off a main power supply (Turn off a breaker).
2) Disconnect the vane motor connector of the direction of the arrow with pressing the unlocking button as shown in figure
below.
Insulate the disconnected connector with the plastic tape.
Horizontal vane
3) Set a vertical vane of the air outlet, which is to be fixed by the hand slowly within the range in the table below.
Measured standard
position of the grille
< Specified range >
Up/down airflow
direction
A
· The vanes can be set between 21mm, 13/16 inch and 30 mm, 1-3/16 inch.
Caution:
Do not set the up/down vanes passed the specified range. Condensation could form and drop from the ceiling,
or the unit could malfunction.
OCH410D
Vane motor
Horizontal vane
Horizontal 30°
Downward 45°
21 mm
25 mm
13/16 inch
31/32 inch
Connector
Downward 55°
Downward 70°
28 mm
30 mm
1-3/32 inch
1-3/16 inch
10
Vane motor
Unlocking button