Operation Details - Panasonic CS-A28BKP5 Service Manual

Room air conditioner
Hide thumbs Also See for CS-A28BKP5:
Table of Contents

Advertisement

CS-A28BKP5/CU-A28BKP5

8 Operation Details

8.1.
Cooling Mode Operation
Cooling in operation according to Remote Control setting.
Time Delay Safety Control (3 minutes)
• When the compressor is stopped by Power Switch, Remote Control or there is a power failure, it restarts after 3 minutes when
the Power Switch, Remote Control is turned ON or the power supply is resumed.
• When the setting temperature is reached during cooling operation, the compressor stops and it will not start for 3 minutes.
7 minutes Time Saved Control
• The compressor will start automatically if it has stopped for 7 minutes even if the room temperature is below the compressor
ON temperature.
Anti-Freezing Control
• If the temperature of the indoor heat exchanger falls
continuously below 2°C for 4 minutes, the compressor turns
off to protect the indoor heat exchanger from freezing. The
fan speed setting remains the same.
• Compressor
recommences
exchanger temperature rises to 10°C (Recovery).
3 minutes waiting of Time Delay Safety Control is
valid for Cooling Operation.
when
the
indoor
heat
12