Mitsubishi Electric MXZ-2A40VA Service Manual page 11

Split-type, heat pump air conditioners outdoor unit
Hide thumbs Also See for MXZ-2A40VA:
Table of Contents

Advertisement

MXZ-2A52VA
Indoor units
combination
Unit A
22
25
35
22+22
22+25
22+35
25+25
25+35
35+35
Indoor units
combination
Unit A
22
25
35
22+22
22+25
22+35
25+25
25+35
35+35
Cooling capacity (kW)
Unit B
2.20
2.50
3.50
2.20
2.20
2.20
2.50
1.93
3.07
2.50
2.50
2.13
2.97
2.60
2.60
Heating capacity (kW)
Unit B
3.30
3.60
4.00
3.05
3.05
2.90
3.30
2.43
3.87
3.15
3.15
2.63
3.67
3.20
3.20
NOTE: Electrical data is for outdoor unit only.
Outdoor unit
power consumption
Total
(kW)
2.2
0.430
(0.9 - 3.0)
(0.120 - 0.620)
2.5
0.490
(0.9 - 3.3)
(0.120 - 0.690)
3.5
0.730
(0.9 - 4.0)
(0.120 - 0.900)
4.4
1.130
(1.1 - 5.3)
(0.250-1.510)
4.7
1.250
(1.1 - 5.4)
(0.250 - 1.560)
5.0
1.400
(1.1 - 5.6)
(0.250 - 1.650)
5.0
1.400
(1.1 - 5.6)
(0.250 - 1.650)
5.1
1.450
(1.1 - 5.8)
(0.250 - 1.740)
5.2
1.505
(1.1 - 6.0)
(0.250 - 1.830)
NOTE: Electrical data is for outdoor unit only.
Outdoor unit
power consumption
Total
3.3
0.670
( 0.9 - 4.0)
(0.110 - 0.910)
3.6
0.730
(0.9 - 4.5)
(0.110 - 1.050)
4.0
0.870
(0.9 - 4.8)
(0.110 - 1.150)
6.1
1.550
(1.0 - 6.7)
(0.200 - 1.730)
6.2
1.600
(1.0 - 6.8)
(0.200 - 1.750)
6.3
1.650
(1.0 - 7.0)
(0.200 - 1.790)
6.3
1.650
(1.0 - 7.0)
(0.200 - 1.790)
6.3
1.650
(1.0 - 7.1)
(0.200 - 1.820)
6.4
1.705
(1.0 - 7.2)
(0.200 - 1.840)
11
Current
(A)
2.08
2.37
3.53
5.12
5.66
6.28
6.28
6.50
6.75
Current
(A)
(kW)
3.24
3.53
4.20
6.95
7.17
7.40
7.40
7.40
7.64
Power
factor
(%)
90
90
90
96
96
97
97
97
97
Power
factor
(%)
90
90
90
97
97
97
97
97
97

Hide quick links: