Indication
No. Symptom
LED1(Red) LED2(Yellow)
Outdoor unit
21
Once
Lighting
operates.
Twice
Lighting
22
3 times
23
Lighting
4 times
Lighting
24
5 times
25
Lighting
Outdoor unit
operates
26
9 times
Lighting
normally.
Lighting
27
Lighting
Abnormal point / Condition
Primary current protection
When the input current exceeds 15A.
Secondary current protection
When the current of the compressor exceeds 15A.
High-pressure protection
When the indoor gas pipe temperature exceeds 45: during heating.
Defrosting in cooling
When the indoor gas pipe temperature falls 3: or below during cooling.
When the frequency of the compressor is kept 80Hz or more and
Discharge temperature
the discharge temperature is kept under 50:(COOL mode)
protection
/40:(HEAT mode) for more than 40 minutes.
When the frequency of the compressor is kept 80Hz or more and
Low discharge
the discharge temperature is kept under 39: for more than 20
temperature protection
minutes.
Cooling high-pressure
When the outdoor heat exchanger temperature exceeds 58:
protection
during operation.
Inverter check mode
When the unit is operated with emergency operation switch.
Normal
Condition
-
61
Correspondence
These symptoms do not mean any abnormality of the
product, but check the following points.
•
Check if indoor filters are clogged.
•
Check if refrigerant is short.
•
Check if indoor/outdoor unit air circulation is short cycled.
•
Check refrigerant circuit and refrigerant amount.
•
Refer to 13-6.D "Check of LEV".
•
Refer to 13-6.F "Check of outdoor thermistors".
•
Refer to 13-6.D "Check of LEV".
•
Check refrigerant circuit and refrigerant amount.
This symptom does not mean any abnormality of the
product, but check the following points.
•
Check if indoor filters are clogged.
•
Check if refrigerant is short.
•
Check if indoor/outdoor unit air circulation is short cycled.
-
-