Standard Operation Data - Mitsubishi Electric PUHZ-HRP200YKA Service Manual

Table of Contents

Advertisement

3-3. Standard operation data

Mode
Capacity
Input
Outdoor unit
Phase, Hz
Voltage
Current
Discharge pressure
Suction pressure
Discharge temperature
Condensing temperature
Suction temperature
Evaporating temperature
Evaporator inlet temperature
Evaporator outlet temperature
Condenser inlet temperature
Condenser outlet temperature
Flow volume
Outlet water temperature
Intake air
temperature
Piping length : Main 2.5m, Branch 2.5m / 2.5m
The unit of pressure has been changed to MPa based on international SI system.
The conversion factor is: 1 (MPa) = 10.2 (kgf/cm²)
3-4. CAPACITY CORRECTION (Refrigerant piping length)
Cooling and heating capacity is lowered according to the piping length. Capacity can be obtained by referring to the following
capacity curves.
Corrected pipe length (m) = actual pipe length (m) + number of bends × 0.3 (m)
100
95
90
85
80
75
70
5
10
15
20
Reference data (connect to Plate HEX)
W
kW
V
A
MPa
MPa
ºC
ºC
ºC
ºC
ºC
ºC
ºC
ºC
L/min
ºC
D.B.
ºC
W.B.
ºC
25
30
35
40
45
50
55
Corrected pipe length [m]
(ACH50-50 plates) o 2 pcs [connected in parallel]
Cooling
(A35/W7)
20,000
9.01
PUHZ-HRP200YKA
13.7
3.0
0.7
79
49
8
6
7
6
——
——
57.3
7
35
24
Cooling
Heating
HRP200
HRP200
60
65
70
75
80
8
Heating
(A7/W35)
23,000
6.31
3, 50
400
9.6
2.0
0.6
73
35
8
2
——
——
65
34
65.9
35
7
6