SW2 setting
Actual water temperature (TH1) on error
occurring
8~39
ON
1
2 3 4 5 6
Pipe temperature / Liquid (TH2) on error
occurring
−39~88
ON
1
2 3 4 5 6
Pressure saturation temperature (T
on error occurring
−39~88
ON
1
2 3 4 5 6
Outdoor pipe temperature / 2-phase.
(TH6) on error occurring
−39~88
ON
1
2 3 4 5 6
Outdoor outside temperature (TH7) on
error occurring
−39~88
ON
1
2 3 4 5 6
Outdoor heatsink temperature (TH8) on
error occurring
ON
−40~200
1
2 3 4 5 6
Discharge superheat on error occurring
SHd
0~255
ON
Cooling = TH4-T
Heating = TH4-T
1
2 3 4 5 6
Sub cool on error occurring SC
0~130
ON
Cooling = T
Heating = T
1
2 3 4 5 6
Display detail
63HS
63HS
63HS
-TH3
63HS
-TH2
63HS
45
Explanation for display
8~39
−39~88
(When the temperature is 0°C or less, "–" and
temperature are displayed by turns.)
(Example) When −15°C;
0.5 secs.
−39~88
)
(When the temperature is 0°C or less, "–" and
temperature are displayed by turns.)
(Example) When −15°C;
0.5 secs.
−39~88
(When the temperature is 0°C or less, "–" and
temperature are displayed by turns.)
(Example) When −15°C;
0.5 secs.
−39~88
(When the temperature is 0°C or less, "–" and
temperature are displayed by turns.)
(Example) When −15°C;
0.5 secs.
−40~200
(When the temperature is 0°C or less, "–" and
temperature are displayed by turns.)
(When the temperature is 100°C or more, hundreds
digit, tens digit and ones digit are displayed by
turns.)
0~255
(When the temperature is 100°C or more, hundreds
digit, tens digit and ones digit are displayed by
turns.)
(Example) When 150°C;
0.5 secs.
0~130
(When the temperature is 100°C or more, hundreds
digit, tens digit and ones digit are displayed by
turns.)
(Example) When 115°C;
0.5 secs.
0.5secs.
2 secs.
15
0.5secs.
2 secs.
15
0.5secs.
2 secs.
15
0.5secs.
2 secs.
15
0.5secs.
2 secs.
1
50
0.5secs.
2 secs.
1
15
Unit
:
:
:
:
:
:
:
: