6-1-4 Set Device Reporting Details

Each device can be set to:
FIRE
FAULT
PRE-ALARM
TRANSPARENT
The default is FIRE reporting.
When the device is activated or reaches its alarm threshold then the event is reported in accordance with
this setting.
FAULT - Primarily intended for use with Input modules, it can allow activation of one input to trigger a fault
report rather than a fire.
PRE-ALARM - Sends warning when the level reported from a detector is 10 below the Alarm threshold.
Used for early warning in sensitive applications.
Transparency Configuration is ONLY applied to Input/Output or Input units. It is not compliant to EN54.

6-1-5 Set Immediate Evacuate for Device

When a detector set to immediate evacuate reports a fire all Sounder Group settings are ignored. All
sounders are operated immediately as if the Sounder Configuration was set to PRESET and all delays are
ignored.
NOTE:
Disabled sounders will not sound.

6-1-6 Device Activation Overrides Delays

Allows a detector to be set to override all zonal and global sounder and I/O delay timers. When this device
is activated the Sounder Groups and I/O Groups associated with this device are also activated
immediately (even if they were already queued for delayed activation).
However this device will not start any of the timers either which means that subsequent fires reported from
other detectors may experience the full delay duration (as programmed).

6-1-7 Inhibit Auxiliary Relays

Allows a specific detector to be set to not operate system I/O's and Auxiliary Relays when it reports a fire.
(Equivalent to pressing auxiliary relays disablement button.)
INSTALLATION & COMMISSIONING MANUAL - REVISION 1.0 - 19.FEB.2007