Manufacturers of Fire Detection Equipment JUNIOR V4-L - FIRE ALARM CONTROL PANEL INSTALLATION & COMMISSIONING MANUAL - V1. 03/2015 OVERVIEW Introduction................................... 6 Key Features................................... 6 Access Levels..................................7 Typical System Schematic..............................8 Power Requirements................................9 Battery Requirements................................. 10 ABS box information................................11...
Page 3
Manufacturers of Fire Detection Equipment JUNIOR V4-L - FIRE ALARM CONTROL PANEL INSTALLATION & COMMISSIONING MANUAL - V1. 03/2015 Sounder Audibility Check..............................Panel....................................Analogue Loop Monitoring.............................. Open Circuit Test................................. Conventional Sounder Monitoring..........................Detector Tests..................................Detector Tests By Zone.............................. Unassigned Detector Test............................
Page 4
Manufacturers of Fire Detection Equipment JUNIOR V4-L - FIRE ALARM CONTROL PANEL INSTALLATION & COMMISSIONING MANUAL - V1. 03/2015 5 Input/Output - Disable & Assign ..........................5-1 Configure I/O Groups..............................5-2 Select Fault I/O Group..............................5-3 Assign I/O Group to Device............................
Page 5
Manufacturers of Fire Detection Equipment JUNIOR V4-L - FIRE ALARM CONTROL PANEL INSTALLATION & COMMISSIONING MANUAL - V1. 03/2015 8 General....................................8-1 Time/Date & Timers..............................8-1-1 Set Date & Time..............................8-1-2 Define Day & Night............................8-1-3 Delays Off at Night............................
Manufacturers of Fire Detection Equipment JUNIOR V4-L - FIRE ALARM CONTROL PANEL INSTALLATION & COMMISSIONING MANUAL - V1. 03/2015 OVERVIEW INTRODUCTION This document covers the installation and commissioning of a JUNIOR fire alarm panel. This document is intended for use by a competent, qualified, fire alarm installation engineer.
Manufacturers of Fire Detection Equipment JUNIOR V4-L - FIRE ALARM CONTROL PANEL INSTALLATION & COMMISSIONING MANUAL - V1. 03/2015 ACCESS LEVEL 1 - General User Unless otherwise indicated, in order to enable the operation of a particular switch, either a valid User or Programming Access Code is required to be entered.
Manufacturers of Fire Detection Equipment JUNIOR V4-L - FIRE ALARM CONTROL PANEL INSTALLATION & COMMISSIONING MANUAL - V1. 03/2015 TYPICAL SYSTEM SCHEMATIC 24 V VOLTAGE FREE NORMALLY OPEN CONTACTS NON-LATCHING ACTION REMOTE DISABLEMENT OF SELECTED DETECTORS CLASS CHANGE REMOTE EVAC.
Manufacturers of Fire Detection Equipment JUNIOR V4-L - FIRE ALARM CONTROL PANEL INSTALLATION & COMMISSIONING MANUAL - V1. 03/2015 BATTERY REQUIREMENTS The battery AH required are calculated from the following formula: Quiescent current in mA of Standby time required in the panel with everything hours divided by 1000.
Manufacturers of Fire Detection Equipment JUNIOR V4-L - FIRE ALARM CONTROL PANEL INSTALLATION & COMMISSIONING MANUAL - V1. 03/2015 ABS BOX INFORMATION MANUFACTURED IN THE E.U. TO THE REQUIREMENTS OF EN54 Pt 2 & Pt 4 1999 QUEUE REVIEW ZONES...
Manufacturers of Fire Detection Equipment JUNIOR V4-L - FIRE ALARM CONTROL PANEL INSTALLATION & COMMISSIONING MANUAL - V1. 03/2015 IDENTIFYING COMPONENTS INSIDE JUNIOR globalfire.pt...
Page 13
Manufacturers of Fire Detection Equipment JUNIOR V4-L - FIRE ALARM CONTROL PANEL INSTALLATION & COMMISSIONING MANUAL - V1. 03/2015 JUNIOR MAIN BOARD FRONT VIEW Junior Expansion Junior Expansion Loop Card Loop Card REAR VIEW globalfire.pt...
Page 14
Manufacturers of Fire Detection Equipment JUNIOR V4-L - FIRE ALARM CONTROL PANEL INSTALLATION & COMMISSIONING MANUAL - V1. 03/2015 NOTE: Junior can only be networked with repeater panels. J-NET-INT-485-NEW INTERFACE FOR RS485 COMMUNICATION J-NET-INT-FO FIBRE OPTIC INTERFACE J-NET-INT-TCP/IP INTERFACE FOR TCP/IP...
Manufacturers of Fire Detection Equipment JUNIOR V4-L - FIRE ALARM CONTROL PANEL INSTALLATION & COMMISSIONING MANUAL - V1. 03/2015 EN54 INFORMATION In accordance with EN54 pt. 2 1997/AC:1999 clause 13.7, the maximum number of sensors and/or manual call points in this panel, will not exceed 512 units.
Manufacturers of Fire Detection Equipment JUNIOR V4-L - FIRE ALARM CONTROL PANEL INSTALLATION & COMMISSIONING MANUAL - V1. 03/2015 RECOMMENDED CABLES Analogue Loops, Conventional Sounders and Data Loops Fire rated Cables for Loops and Sounder Circuits AEI type Firetec Multicore Ref. F1C1 (1 mm ) to F1C2.5 (2.5 mm ) in 2 core AEI type Firetec Armoured Ref.
Manufacturers of Fire Detection Equipment JUNIOR V4-L - FIRE ALARM CONTROL PANEL INSTALLATION & COMMISSIONING MANUAL - V1. 03/2015 DEFINITIONS Analogue Loop The physical link, usually fireproof 2 conductor shielded wiring cable, forming a ring of interconnection between sensors and the detection panel.
Manufacturers of Fire Detection Equipment JUNIOR V4-L - FIRE ALARM CONTROL PANEL INSTALLATION & COMMISSIONING MANUAL - V1. 03/2015 INSTALLATION INTRODUCTION This section covers the physical installation of the system. It primarily focuses on the parts that are required and how they should be connected together. Do not connect the mains power or the batteries at this stage;...
Manufacturers of Fire Detection Equipment JUNIOR V4-L - FIRE ALARM CONTROL PANEL INSTALLATION & COMMISSIONING MANUAL - V1. 03/2015 PANEL MAIN BOARD - CONNECTION DEFINITIONS JUNIOR MAIN BOARD Loop connections. A1 corresponds to Loop 1 and A2 to Loop 2...
Manufacturers of Fire Detection Equipment JUNIOR V4-L - FIRE ALARM CONTROL PANEL INSTALLATION & COMMISSIONING MANUAL - V1. 03/2015 FITTING JUNIOR EXPANSION LOOP CARD 1 - This operation should only be performed by qualified personnel. 2 - Power to the panel should be completely removed, both primary and secondary (batteries) supplies, before the installation process of the card is initiated.
Manufacturers of Fire Detection Equipment JUNIOR V4-L - FIRE ALARM CONTROL PANEL INSTALLATION & COMMISSIONING MANUAL - V1. 03/2015 DATA LOOPS If the system includes mini-repeaters to allow remote viewing and control of the system, an RS422/485, Fibre Optic or TCP/IP connection may be used.
Manufacturers of Fire Detection Equipment JUNIOR V4-L - FIRE ALARM CONTROL PANEL INSTALLATION & COMMISSIONING MANUAL - V1. 03/2015 PANEL RS485 NOTE: Make all connections with the power turned off to avoid risk of permanent damage to the circuit boards.
Manufacturers of Fire Detection Equipment JUNIOR V4-L - FIRE ALARM CONTROL PANEL INSTALLATION & COMMISSIONING MANUAL - V1. 03/2015 REPEATER RS485 NOTE: Make all connections with the power turned off to avoid risk of permanent damage to the circuit boards.
Manufacturers of Fire Detection Equipment JUNIOR V4-L - FIRE ALARM CONTROL PANEL INSTALLATION & COMMISSIONING MANUAL - V1. 03/2015 PANEL FIBRE-OPTIC NOTE: Make all connections with the power turned off to avoid risk of permanent damage to the circuit boards.
Manufacturers of Fire Detection Equipment JUNIOR V4-L - FIRE ALARM CONTROL PANEL INSTALLATION & COMMISSIONING MANUAL - V1. 03/2015 REPEATER FIBRE-OPTIC NOTE: Make all connections with the power turned off to avoid risk of permanent damage to the circuit boards.
Manufacturers of Fire Detection Equipment JUNIOR V4-L - FIRE ALARM CONTROL PANEL INSTALLATION & COMMISSIONING MANUAL - V1. 03/2015 TCP/IP Connection The use of a TCP/IP network may require the support and co-operation of the end users IT department. Be sure that this support is available before deciding on this communications method.
Manufacturers of Fire Detection Equipment JUNIOR V4-L - FIRE ALARM CONTROL PANEL INSTALLATION & COMMISSIONING MANUAL - V1. 03/2015 CONVENTIONAL SOUNDERS Conventional Sounders is the term used to describe conventional alarm sounders (or bells) connected directly to a Panel. Loop-powered Sounders are different and are connected to the Analogue Loop.
Manufacturers of Fire Detection Equipment JUNIOR V4-L - FIRE ALARM CONTROL PANEL INSTALLATION & COMMISSIONING MANUAL - V1. 03/2015 PANEL BATTERIES It is recommended that the batteries are fitted at the end of commissioning the system otherwise it can be difficult to remove the power quickly if there is a problem.
Manufacturers of Fire Detection Equipment JUNIOR V4-L - FIRE ALARM CONTROL PANEL INSTALLATION & COMMISSIONING MANUAL - V1. 03/2015 COMMISSIONING INTRODUCTION Commissioning involves checking that all connections have been made properly and that all hardware is functioning correctly. This means the system must first be installed in accordance with the previous section of this manual.
Page 30
Manufacturers of Fire Detection Equipment JUNIOR V4-L - FIRE ALARM CONTROL PANEL INSTALLATION & COMMISSIONING MANUAL - V1. 03/2015 CONTROLS BUZZER SILENCE The occurrence of any new fire or fault condition will initiate the operation of the internal buzzer. By pressing this switch, the operation of the buzzer will be stopped until a new fire or fault appears on the system.
Page 31
Manufacturers of Fire Detection Equipment JUNIOR V4-L - FIRE ALARM CONTROL PANEL INSTALLATION & COMMISSIONING MANUAL - V1. 03/2015 QUEUE REVIEW FIRE - General User Access (no code entry required) If more than one fire has been detected then the LED next to this button will flash. Press the button to step through all detected fires.
Manufacturers of Fire Detection Equipment JUNIOR V4-L - FIRE ALARM CONTROL PANEL INSTALLATION & COMMISSIONING MANUAL - V1. 03/2015 GETTING THE PANEL RUNNING Apply AC power to the Panel. The LCD should display the software version and the message ‘INITIALIZING’ . This will be followed by the date and time (and the company name if it has been set).
Manufacturers of Fire Detection Equipment JUNIOR V4-L - FIRE ALARM CONTROL PANEL INSTALLATION & COMMISSIONING MANUAL - V1. 03/2015 GETTING INTO PROGRAMMING MODE (ACCESS LEVEL 3) When the Panel is powered up it will be necessary to enter the panel programming mode. Familiarize yourself with this section before proceeding to the next section in the manual and powering up the panel.
Manufacturers of Fire Detection Equipment JUNIOR V4-L - FIRE ALARM CONTROL PANEL INSTALLATION & COMMISSIONING MANUAL - V1. 03/2015 GETTING THE SYSTEM RUNNING Ensure all connectors are firmly in place. Ensure that all connections are tight, with no stray strands of wire.
Manufacturers of Fire Detection Equipment JUNIOR V4-L - FIRE ALARM CONTROL PANEL INSTALLATION & COMMISSIONING MANUAL - V1. 03/2015 Note that there is no clear end to Installation mode because the system is constantly looking and learning. However if the system is put into Active Mode and Installation Mode hasn’t had time to identify all system components you will very quickly be greeted with error reports regarding unexpected devices.
Manufacturers of Fire Detection Equipment JUNIOR V4-L - FIRE ALARM CONTROL PANEL INSTALLATION & COMMISSIONING MANUAL - V1. 03/2015 Conventional Sounder Monitoring Panels have two Conventional Sounder circuits. Check the Conventional Sounder circuits for open and short circuit fault detection.
Manufacturers of Fire Detection Equipment JUNIOR V4-L - FIRE ALARM CONTROL PANEL INSTALLATION & COMMISSIONING MANUAL - V1. 03/2015 Unassigned Detector Tests If the detectors have not been assigned to a Zone then they can only be tested in normal (Active) mode. Using the programming menu ensure the system is set to Active Mode then exit programming mode and press SYSTEM RESET.
Manufacturers of Fire Detection Equipment JUNIOR V4-L - FIRE ALARM CONTROL PANEL INSTALLATION & COMMISSIONING MANUAL - V1. 03/2015 Battery Fault Message Test This test should be performed for each set of batteries. Test only the actual battery connections. Panel Main Board MANUFACTURED IN THE E.U.
Manufacturers of Fire Detection Equipment JUNIOR V4-L - FIRE ALARM CONTROL PANEL INSTALLATION & COMMISSIONING MANUAL - V1. 03/2015 ADVANCED FUNCTIONALITY PROGRAMMING FUNCTIONS GENERAL Complete List of Functions 1 Review Historic Log 6-3 Discovery Specific - Functions only available 1-1 Display Historic Log...
Manufacturers of Fire Detection Equipment JUNIOR V4-L - FIRE ALARM CONTROL PANEL INSTALLATION & COMMISSIONING MANUAL - V1. 03/2015 Keys To Use Within Functions Most functions use some or all of the following keys: are used to browse through items.
Manufacturers of Fire Detection Equipment JUNIOR V4-L - FIRE ALARM CONTROL PANEL INSTALLATION & COMMISSIONING MANUAL - V1. 03/2015 SPECIFIC FUNCTIONS General Because of the flexibility and functionality of this panel it can sometimes be quite hard to establish your desired configuration.
Manufacturers of Fire Detection Equipment JUNIOR V4-L - FIRE ALARM CONTROL PANEL INSTALLATION & COMMISSIONING MANUAL - V1. 03/2015 Zones - Disable & Assign All the functions associated with managing Zones 3-1 Disable Zones Allows you to disable or enable Zones.
Manufacturers of Fire Detection Equipment JUNIOR V4-L - FIRE ALARM CONTROL PANEL INSTALLATION & COMMISSIONING MANUAL - V1. 03/2015 Sounders - Disable & Assign 4-1 Sounder Configuration Allows selection of PRESET or PROGRAMMED sounder operation. Selecting PRESET (the default) will result in all sounders being operated; any Sounder Group settings will be ignored.
Manufacturers of Fire Detection Equipment JUNIOR V4-L - FIRE ALARM CONTROL PANEL INSTALLATION & COMMISSIONING MANUAL - V1. 03/2015 4-3 Disable Sounders Allows specific sounders to be disabled or Enabled. Disabled sounders will not be operated regardless of Sounder Configuration, Sounder Groups and evacuate requests.
4-6 Sounder Delay Set-up Allows the sounder delay to be set-up: The sounder delay can be set to GLOBAL MODE, ZONAL MODE or DISABLED. The sounder delay period is defined (to a maximum of 10 minutes). The devices that initiate a delayed sounder activation are specified.
Manufacturers of Fire Detection Equipment JUNIOR V4-L - FIRE ALARM CONTROL PANEL INSTALLATION & COMMISSIONING MANUAL - V1. 03/2015 Input/Output - Disable & Assign Input/Output Analogue Loop device management. 5-1 Configure I/O Groups Allows an I/O Group to be established. The I/O Group can then be used for fire or fault reporting. 512 I/O Groups can be defined.
Manufacturers of Fire Detection Equipment JUNIOR V4-L - FIRE ALARM CONTROL PANEL INSTALLATION & COMMISSIONING MANUAL - V1. 03/2015 5-4 Inhibit I/O for Device Allows a device to be set so that it does not operate certain I/O Groups. The options are:...
Manufacturers of Fire Detection Equipment JUNIOR V4-L - FIRE ALARM CONTROL PANEL INSTALLATION & COMMISSIONING MANUAL - V1. 03/2015 Device Set-up Allows specific settings to be selected for individual Analogue Loop devices. 6-1 General Settings common to all types of Analogue Loop devices.
6-1-6 Device Activation Overrides Delays Allows a detector to be set to override all zonal and global sounder and I/O delay timers. When this device is activated the Sounder Groups and I/O Groups associated with this device are also activated immediately (even if they were already queued for delayed activation).
INSTALLATION & COMMISSIONING MANUAL - V1. 03/2015 6-1-8 Global Sensitivity Set-up This function selects the sensitivity of all the detectors that have been set to GLOBAL SENSITIVITY. Different settings can be entered for weekdays and for Saturday and Sunday. Settings are :...
Each individual detector has the following settings: NORMAL HIGH GLOBAL If GLOBAL is selected then, depending the day, the appropriate HIGH, LOW, NORMAL or TIMED setting is used (see functions 6-1-8 Global Sensitivity Set-up and 6-1-9 Configure Timed Sensitivity). HIGH NORMAL The Pre-alarm levels are always 10 below the alarm thresholds.
Settings are MODE 1, MODE 3, MODE 5 or GLOBAL. If GLOBAL is selected then, depending on the day, the appropriate HIGH, LOW, NORMAL or TIMED setting is used (see functions 6-1-8 Global Sensitivity Set-up and 6-1-9 Configure Timed Sensitivity).
Page 53
Manufacturers of Fire Detection Equipment JUNIOR V4-L - FIRE ALARM CONTROL PANEL INSTALLATION & COMMISSIONING MANUAL - V1. 03/2015 6-3-5 Check for Devices Needing Service When activated this function reads the drift compensation value of every Discovery™ device connected to the system.
Manufacturers of Fire Detection Equipment JUNIOR V4-L - FIRE ALARM CONTROL PANEL INSTALLATION & COMMISSIONING MANUAL - V1. 03/2015 6-4 Automatic Address Setting (ASET) - Wizmart Protocol only Introduction Automatic Address Setting (ASET) is a special install and commissioning mode that can be activated on a per loop basis whilst in INSTALLATION mode.
Manufacturers of Fire Detection Equipment JUNIOR V4-L - FIRE ALARM CONTROL PANEL INSTALLATION & COMMISSIONING MANUAL - V1. 03/2015 In order to initiate the programming procedure of the SAM’s the Panel has to be in INSTALLATION MODE. See function 8.4.1.
Manufacturers of Fire Detection Equipment JUNIOR V4-L - FIRE ALARM CONTROL PANEL INSTALLATION & COMMISSIONING MANUAL - V1. 03/2015 This procedure is then repeated for each blank SAM on the loop. There should be a time interval of approx. 10 seconds between SAM activations.
Manufacturers of Fire Detection Equipment JUNIOR V4-L - FIRE ALARM CONTROL PANEL INSTALLATION & COMMISSIONING MANUAL - V1. 03/2015 TROUBLESHOOTING a) SAM does not program If during the course of programming a SAM, the new address is not programmed in the module, verify that the connections to both the loop and the conventional device are correctly made.
Manufacturers of Fire Detection Equipment JUNIOR V4-L - FIRE ALARM CONTROL PANEL INSTALLATION & COMMISSIONING MANUAL - V1. 03/2015 Monitor Device Counts & Test 7-1 Device Count, Type & Value Use this function to check that all loop devices are present.
Manufacturers of Fire Detection Equipment JUNIOR V4-L - FIRE ALARM CONTROL PANEL INSTALLATION & COMMISSIONING MANUAL - V1. 03/2015 General 8-1 Time/Date & Timers 8-1-1 Set Date & Time Allows the date and time for the system to be set. The date and time is displayed on the LCD whilst the system is not in fault or fire.
In DEVICE MODE the evacuate timer is started when a device that has been configured to start the Evacuate Timer detects a fire. In GLOBAL MODE the Evacuate Timer is started when any device detects a fire. NOTE: For DEVICE MODE to work at least one device must be set to start the timer. See programming function 8-1-5.
Manufacturers of Fire Detection Equipment JUNIOR V4-L - FIRE ALARM CONTROL PANEL INSTALLATION & COMMISSIONING MANUAL - V1. 03/2015 8-2-2 Call Points to Evacuate. Enables or disables a system wide setting that a report of fire from a call-point automatically starts evacuation.
Manufacturers of Fire Detection Equipment JUNIOR V4-L - FIRE ALARM CONTROL PANEL INSTALLATION & COMMISSIONING MANUAL - V1. 03/2015 8-3-2 Clear Non-Volatile RAM Clearing the NVRAM clears all the installation settings and the system is automatically put into Installation Mode. On the Panel this will result in:...
Manufacturers of Fire Detection Equipment JUNIOR V4-L - FIRE ALARM CONTROL PANEL INSTALLATION & COMMISSIONING MANUAL - V1. 03/2015 8-4 Other Features These are programming functions that do not fall into any other category. 8-4-1 Active/Installation Mode An essential function. The system should always be left in ACTIVE mode, unless the system is being installed and debugged.
Manufacturers of Fire Detection Equipment JUNIOR V4-L - FIRE ALARM CONTROL PANEL INSTALLATION & COMMISSIONING MANUAL - V1. 03/2015 The PC Loader Software ® The PC Loader software is runs under Windows (98, 98SE, Me, 2000 and XP). Communications to the panel is through one of the serial communication ports (COMM PORT) and in order to install it, the only requirement is to double click on the installer package supplied and follow the supplied instructions.
Manufacturers of Fire Detection Equipment JUNIOR V4-L - FIRE ALARM CONTROL PANEL INSTALLATION & COMMISSIONING MANUAL - V1. 03/2015 8-4-4 Set User Access Code This function allows the installer to change the customer Access Code. Use pq to change code sequence.
Manufacturers of Fire Detection Equipment JUNIOR V4-L - FIRE ALARM CONTROL PANEL INSTALLATION & COMMISSIONING MANUAL - V1. 03/2015 TECHNICAL SPECIFICATIONS Please note that these specifications apply to the Junior Analogue Addressable panel, 1 or 2 loop models, equipped with a 2.4 Amp power supply @ 28.5V DC nominal.
Page 67
Manufacturers of Fire Detection Equipment JUNIOR V4-L - FIRE ALARM CONTROL PANEL INSTALLATION & COMMISSIONING MANUAL - V1. 03/2015 Maximum Continuous Primary Power Supply Rating 2.4 Amps @ 28,5 V DC nominal, comprising: 1 Amp max. temperature compensated, short circuit protected, battery charger.
Page 68
6.1, that the power supply equipment included in our analogue addressable fire alarm panel named JUNIOR V4-L, has been designed in accordance with a quality management system which incorporates a set of rules for the design of all elements of the p.s.e., and that its components have been selected for the intended...
Page 69
Manufacturers of Fire Detection Equipment JUNIOR V4-L - FIRE ALARM CONTROL PANEL INSTALLATION & COMMISSIONING MANUAL - V1. 03/2015 globalfire.pt...
Page 70
Manufacturers of Fire Detection Equipment JUNIOR V4-L - FIRE ALARM CONTROL PANEL INSTALLATION & COMMISSIONING MANUAL - V1. 03/2015 globalfire.pt...