Analogue Loop - Global JUNIOR V4 Installation & Commissioning Manual

Fire alarm control panel
Table of Contents

Advertisement

TCP/IP Connection
The use of a TCP/IP network may require the support and co-operation of the end users IT department. Be
sure that this support is available before deciding on this communications method
Analogue Loop(s)
The Analogue Loop provides the connection to all
the analogue addressable devices and loop
powered sounders. Unless the loop is completed
the panel will not be able to monitor its integrity
(open and short circuit monitoring).
Connection to the Analogue Loop for the Junior
panel is shown below:
Devices that can be fitted to the Analogue Loop
include smoke sensors, heat sensors, Zone
Monitor Units (ZMU), I/O units, loop sounders
and manual call-points.
Wire the loop as shown.
Make the connections to the devices as specified on the device data sheet. If no data sheet is available
make the connections as below:
NOTE:
A maximum of 32 manual call-points can be fitted to the loop. If this value is exceeded the
response time for certain types of call-point will be excessive.
INSTALLATION & COMMISSIONING MANUAL - REVISION 1.0 - 19.FEB.2007
INSTALLATION
For detailed TCP/IP connection
information please refer to TCP/IP
specific technical information
and/or contact technical support at
techs@globalfire.pt
Device 1
Loop 1
Loop 2
Connector
Connector
DEVICES
Device 2
25